EM15 User’s Manual
3. Installation of Frequency Inverter
19
Frequency inverter
Model
MCCB
(A)
Contactor
(A)
Cable of Input Side
Main Circuit
(mm2)
Cable of Output Side
Main Circuit
(mm2)
Cable of Control
Circuit
(mm2)
EM15- G2-022
200
125
25
25
1.0
EM15- G2-030
200
125
35
25
1.0
EM15- G2-037
250
160
50
35
1.0
EM15- G2-045
250
160
70
35
1.0
EM15- G2-055
350
350
120
120
1.0
EM15- G2-075
500
400
185
185
1.0
Three-phase 380V
EM15B- G3-d75/P3-1d5
10
10
2.5
2.5
1.0
EM15B- G3-1d5/P3-2d2
16
10
2.5
2.5
1.0
EM15B- G3-2d2/P3-004
16
10
2.5
2.5
1.0
EM15- G3-004/P3-5d5
25
16
4.0
4.0
1.0
EM15- G3-5d5/P3-7d5
32
25
4.0
4.0
1.0
EM15- G3-7d5/P3-011
40
32
4.0
4.0
1.0
EM15- G3-011/P3-015
63
40
4.0
4.0
1.0
EM15- G3-015/P3-018
63
40
6.0
6.0
1.0
EM15- G3-018/P3-022
100
63
6
6
1.0
EM15- G3-022/P3-030
100
63
10
10
1.0
EM15- G3-030/P3-037
125
100
16
10
1.0
EM15- G3-037/P3-045
160
100
16
16
1.0
EM15- G3-045/P3-055
200
125
25
25
1.0
EM15- G3-055/P3-075
250
125
35
25
1.0
EM15- G3-075/P3-090
250
160
50
35
1.0
EM15- G3-090/P3-110
350
160
70
35
1.0
EM15- G3-110/P3-132
350
350
120
120
1.0
EM15- G3-132/P3-160
400
400
150
150
1.0
EM15- G3-160/P3-200
500
400
185
185
1.0
EM15- G3-200/P3-220
630
600
150*2
150*2
1.0
EM15- G3-220/P3-250
630
600
150*2
150*2
1.0
EM15- G3-250/P3-280
800
600
185*2
185*2
1.0
EM15- G3-280/P3-315
800
800
185*2
185*2
1.0
EM15- G3-315/P3-355
1000
800
150*3
150*3
1.0
EM15- G3-355/P3-400
1000
800
150*4
150*4
1.0
EM15- G3-400/P3-450
1200
1000
150*4
150*4
1.0
EM15-G3-450--
1200
1200
150*4
150*4
1.0
3.6 Removal and mounting of operating panel and cover
3.6.1 Removal and mounting of operating panel (keypad)
The operating panel of EM15 series frequency inverter is a plug type, If you need to take it off when use or
maintenance, please make sure the gentle actions, or it is easy to damage the plug type connection terminals on
operating panel.
The removal and mounting of operating panel (keypad) is showed as Diagram3-3 and Diagram3-4: