background image

47

PRESSURE TEMPERATURE CHART AT SEA LEVEL

Red (Bar)=Vacuum

 

Black (Bar)=Vapor

 Bold (Bar)=Liquid

o

C

R12

R22

R-134a

R407A 

Vapor

R407A 

Liquid

R404A 

HP 62

R407C 

Vapor

R407C 

Liquid

R408A

R409A

R410A

R502

R507A 

AZ50"

o

F

-45.6

0.53

0.21

0.63

0.30

0.03

0.00

0.37

0.09

0.07

0.63

0.34

-0.03

0.06

-50.0

-44.4

0.49

0.16

0.61

0.26

0.03

0.05

0.33

0.04

0.02

0.61

0.41

0.02

0.12

-48.0

-43.3

0.47

0.12

0.59

0.22

0.08

0.11

0.29

0.01

0.04

0.58

0.48

0.08

0.18

-46.0

-42.2

0.44

0.06

0.56

0.17

0.14

0.17

0.25

0.07

0.10

0.56

0.57

0.14

0.24

-44.0

-41.1

0.41

0.01

0.53

0.12

0.21

0.23

0.20

0.13

0.15

0.53

0.65

0.19

0.30

-42.0

-40.0

0.37

0.04

0.50

0.07

0.27

0.30

0.16

0.19

0.21

0.50

0.74

0.26

0.37

-40.0

-38.9

0.34

0.10

0.47

0.01

0.34

0.37

0.11

0.26

0.28

0.47

0.83

0.32

0.44

-38.0

-37.8

0.30

0.15

0.44

0.04

0.41

0.43

0.06

0.32

0.34

0.44

0.92

0.39

0.52

-36.0

-36.7

0.27

0.21

0.41

0.10

0.48

0.51

0.00

0.39

0.41

0.41

1.01

0.46

0.59

-34.0

-35.6

0.23

0.28

0.37

0.16

0.56

0.59

0.06

0.46

0.48

0.37

1.12

0.53

0.68

-32.0

-34.4

0.19

0.34

0.33

0.23

0.63

0.66

0.11

0.53

0.55

0.34

1.22

0.60

0.75

-30.0

-33.3

0.15

0.41

0.29

0.29

0.72

0.74

0.17

0.61

0.63

0.30

1.33

0.68

0.84

-28.0

-32.2

0.10

0.48

0.25

0.36

0.80

0.83

0.23

0.69

0.71

0.26

1.44

0.76

0.93

-26.0

-31.1

0.06

0.55

0.21

0.43

0.89

0.92

0.30

0.77

0.79

0.22

1.56

0.84

1.02

-24.0

-30.0

0.01

0.63

0.17

0.51

0.98

1.01

0.37

0.86

0.88

0.17

1.68

0.93

1.12

-22.0

-28.9

0.03

0.70

0.13

0.59

1.08

1.10

0.45

0.94

0.97

0.13

1.81

1.01

1.21

-20.0

-27.8

0.09

0.79

0.08

0.67

1.17

1.20

0.52

1.04

1.06

0.08

1.94

1.11

1.32

-18.0

-26.7

0.14

0.87

0.03

0.75

1.28

1.30

0.60

1.14

1.15

0.03

2.07

1.20

1.42

-16.0

-25.6

0.19

0.96

0.02

0.84

1.38

1.41

0.68

1.23

1.25

0.02

2.21

1.30

1.53

-14.0

-24.4

0.25

1.05

0.08

0.93

1.49

1.52

0.77

1.34

1.35

0.07

2.35

1.40

1.64

-12.0

-23.3

0.31

1.14

0.13

1.03

1.60

1.63

0.85

1.44

1.46

0.12

2.50

1.51

1.76

-10.0

-22.2

0.37

1.23

0.19

1.12

1.72

1.74

0.94

1.55

1.57

0.18

2.66

1.61

1.88

-8.0

-21.1

0.43

1.34

0.25

1.23

1.83

1.86

1.03

1.67

1.68

0.24

2.81

1.73

2.00

-6.0

-20.0

0.50

1.44

0.32

1.33

1.96

1.99

1.13

1.79

1.79

0.30

2.98

1.84

2.13

-4.0

-18.9

0.56

1.54

0.38

1.44

2.09

2.12

1.23

1.91

1.91

0.37

3.15

1.96

2.26

-2.0

-17.8

0.63

1.66

0.45

1.55

2.22

2.25

1.34

2.03

2.03

0.43

3.32

2.08

2.40

0.0

-16.7

0.70

1.77

0.52

1.67

2.36

2.39

1.45

2.17

2.16

0.50

3.50

2.21

2.54

2.0

-15.6

0.77

1.89

0.59

1.79

2.50

2.52

1.56

2.30

2.29

0.57

3.69

2.34

2.68

4.0

-14.4

0.85

2.01

0.66

1.92

2.65

2.67

1.68

2.43

2.43

0.65

3.88

2.48

2.83

6.0

-13.3

0.92

2.14

0.74

2.05

2.80

2.82

1.80

2.58

2.57

0.72

4.08

2.61

2.99

8.0

-12.2

1.01

2.26

0.82

2.18

2.95

2.97

1.92

2.72

2.71

0.80

4.29

2.76

3.15

10.0

-11.1

1.09

2.40

0.90

2.32

3.11

3.13

2.05

2.88

2.86

0.88

4.50

2.90

3.31

12.0

-10.0

1.17

2.54

0.99

2.46

3.28

3.30

2.19

3.03

3.01

0.97

4.72

3.06

3.48

14.0

-8.9

1.26

2.68

1.08

2.61

3.45

3.46

2.32

3.19

3.17

1.06

4.94

3.21

3.66

16.0

-7.8

1.35

2.82

1.17

2.76

3.62

3.63

2.46

3.36

3.32

1.14

5.17

3.37

3.83

18.0

-6.7

1.45

2.97

1.27

2.92

3.80

3.81

2.61

3.53

3.49

1.24

5.41

3.53

4.01

20.0

-5.6

1.54

3.12

1.37

3.08

3.99

4.00

2.77

3.71

3.66

1.34

5.65

3.70

4.21

22.0

-4.4

1.64

3.28

1.47

3.25

4.18

4.19

2.92

3.89

3.84

1.43

5.90

3.88

4.40

24.0

-3.3

1.74

3.45

1.58

3.42

4.37

4.38

3.08

4.08

4.02

1.54

6.15

4.06

4.60

26.0

-2.2

1.85

3.61

1.69

3.60

4.57

4.58

3.25

4.27

4.21

1.65

6.42

4.23

4.80

28.0

-1.1

1.96

3.79

1.80

3.78

4.78

4.78

3.42

4.46

4.39

1.76

6.69

4.43

5.01

30.0

0.0

2.07

3.97

1.92

3.97

4.99

4.99

3.59

4.67

4.59

1.87

6.97

4.62

5.23

32.0

1.1

2.18

4.15

2.03

4.17

5.21

5.21

3.78

4.88

4.79

1.99

7.26

4.81

5.45

34.0

2.2

2.30

4.34

2.16

4.37

5.43

5.43

3.97

5.09

5.00

2.10

7.55

5.02

5.68

36.0

3.3

2.42

4.53

2.28

4.57

5.67

5.66

4.16

5.31

5.21

2.23

7.86

5.23

5.91

38.0

4.4

2.54

4.73

2.41

4.79

5.90

5.89

4.36

5.53

5.43

2.36

8.17

5.44

6.15

40.0

5.6

2.67

4.93

2.55

5.00

6.14

6.12

4.56

5.77

5.65

2.49

8.48

5.66

6.39

42.0

6.7

2.80

5.14

2.69

5.23

6.40

6.37

4.77

6.00

5.88

2.62

8.81

5.89

6.65

44.0

7.8

2.94

5.35

2.83

5.46

6.66

6.62

4.99

6.25

6.12

2.77

9.14

6.12

6.90

46.0

8.9

3.08

5.57

2.98

5.70

6.92

6.88

5.21

6.50

6.36

2.90

9.48

6.35

7.17

48.0

Summary of Contents for ZX Platform Condensing Unit

Page 1: ...ZX Platform Condensing Unit Product Manual ...

Page 2: ...e is embellished with a record of unmissed annual dividend for 55 consecutive years For FY11 Emerson was ranked No 120 on Fortune 500 a list of America s largest companies and placed No 1 in the same list s Electronics and Equipment category The company invested approximately 696 million in engineering development and customer solutions development producing 773 patents worlwide from FY04 to FY10 ...

Page 3: ...2 Controller Trip Set Points and Actions ZX MT and ZXL LT Units 16 ZXD Controller Assembly 18 ZXD Electronic Controller 19 Alarm Messaging Digital Scroll Controller ZXD 23 CapacityandPower kW ZXFamily MediumTemperature R22 50Hz 24 60Hz 25 ZXFamily MediumTemperature R404A R507 50Hz 26 60Hz 27 ZXDFamily DigitalMediumTemperature R22 50 Hz 28 ZXDFamily DigitalMediumTemperature R404A R507 50 Hz 29 60 H...

Page 4: ...uously for7 days 24 hours and 365 days The ZX and ZXI compressors injection scheme and heat exchanger designs are optimized to provide best efficiencies at annual averaged temperature rather than at typical rating conditions The typical ambient on an annual basis follows a normal distribution pattern The highest and lowest ambient happens only for few hours as shown in figure 01 Hours Low Ambient ...

Page 5: ...ature models Operating ambient is 48 C to 23 C Proprietary Electronic Algorithms to Control Fan Speed Optimizing Energy Performance for Local Seasonal Ambient Temperatures Copeland Scroll Compressor Technology High Efficiency Ultra Quiet High Reliability Variable Speed PSC Fan Motors High Efficiency Ultra Quiet Optimizes Air Flow for Maximum Heat Transfer Oversized Condenser Coil for Maximum Heat ...

Page 6: ...ce formation on the evaporator coils frost build up Lower frost build up improves the evaporator heat exchange efficiency Italsoreducesthedefrostheatdemand therebyresultinginlowerenergy neededfordefrost 3 Freshness of food Another benefit of higher evaporating temperature is reduced dehumidification by the evaporator coil This allows higher relative humidity in cold room or cold cases Higher relat...

Page 7: ...Base Model Electrical Code Bill of Material BOM CDU Family ZX ZXL ZXD BOM 401 451 451 461 471 450 451 461 Liquid Line Filter Dryer Sight Glass Oil Separator Accumulator Adjustable LP Switch Fixed LP Switch E2 Controller Diagnostic Module Buzzer Digital Scroll Controller Fan Speed Controller Circuit Breaker Sound Jacket Defrost Module ACC ACC ACC ACC Filter Drier V Notes E2 controller has fan speed...

Page 8: ...ture 0 C 10 48 43 2 1 0 1 5 1 0 2 5 0 10 Evaporating Temperature 0 C ZXD Digital Medium Temperature at 50 Hz TFD at 60 Hz TF7 1 Note For model ZXD075 E Max Amb 43 C Max Evap 5 C R404A R507 18 C RGT R404A R507 10K SH R22 10K SH 1 1 1 ZXD Family Digital Medium Temperature Ambient Temperatu 10 20 15 12 5 10 Evaporating Temperature 0 C Fan Speed Control Function For Ambient Lower Than 10 0 C 1 Note Fo...

Page 9: ...l features which are part of a well designed condensing unit ZX MT ZXL LT E2 Controller ZXD Digital Scroll Controller Scroll Compressor Figure 05 Identifies the electronic controller assembly on a ZX Platform CDU Figure 06 Identifies other major components layout on a ZX Platform CDU Oil Separator Optional In MT CDU Liquid Receiver Liquid Sight Glass Moisture Indicator Liquid Filter Drier Suction ...

Page 10: ...h an economizer refrigeration cycle Vapor injection eliminates the need for liquid injection which would otherwise have been required to operate a reliable LT envelope down to 40 C evaporating temperature In vapor injection a part of liquid refrigerant is expanded and passed through a heat exchanger In the heat exchanger this expanded refrigerant absorbs heat from the main liquid line and sub cool...

Page 11: ...ity range through which this particular unit will need to operate Follow the ASHRAE guidelines for proper piping practices Location and Fixing The unit should always be installed in a location that ensures clean air flow It is recommended that a clearance of 300 mm from the wall or the next unit be maintained from the unit s left and rear panels whereas a clearance of 500 mm must be maintained fro...

Page 12: ...erate Pipe runs should be kept as short as possible using the minimum number of directional changes Use large radius bends and avoid trapping of oil and refrigerant This is particularly important for the suction line The suction line should ideally slope gently towards the unit Recommendation slope is 1 200 1 250 P traps double risers and reduced pipe diameters may be required for suction lines wh...

Page 13: ...trap some oil and in some cases it may be necessary to add oil if pipes are long if the vertical rise is high and if the piping is not well designed The oil level should be monitored carefully during commissioning checked after 4 8 hours and checked again after 24 hours of normal operation The ideal oil level is between and sight glass level but if any oil is visible in the sight glass the compres...

Page 14: ...ion of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized Reverse rotation of a scroll compressor also results in substantially reduced current draw compared to specification sheet values Suction temperature will be high discharge temperature will be low and the compressor may be abnormally noisy There is no nega...

Page 15: ...the compressor trips Two problems arise due to internal protector trip First there is no alarm to detect the trip and second a compressor internal protector reset may take as long as an hour This could be critical for the quality of frozen food in freezers or cases On the other hand ZXL E2 controller detects the overload externally and actions a temporary shutdown E2 Diagnostics will then start tr...

Page 16: ...or Contactor Diagnostic Module Fuse Holder Electrical Cable connectors Defrost Module optional Defrost Duration in Minutes Defrost Interval In Hours E2 Connector Manual Defrost Button Remote Connector For Manual Defrost E2 Display Diagnostic Remote Buzzer With Volume E2 Display Diagnostic Remote Buzzer With Volume ...

Page 17: ...h Pressure Switch Connector J3 Low Pressure Switch Connector J5 Defrost Module Connector E2 Control Board J1 EXV Driver Connector J2 Diagnosis Module Connector S2 Evaporator Fan Mode Setting Dip Switch S3 Compressor Current Sensing Hi Lo Setting Dip Switch JP13 Compressor Contactor Coil JP12 Liquid Line Solenoid Vlave Coil JP11 Condenser Fan Motor JP10 Defrost Heater Contactor or Relay JP9 Evap Fa...

Page 18: ...0 E 760 E TFD 6 OFF ON ON ZX0200 E TF5 1 ON ON ON ZX0300 E TF5 2 ON ON ON ZX0400 E TF5 3 ON ON ON ZX0500 E TF5 4 ON OFF OFF ZX0600 E TF5 5 ON OFF OFF ZX0750 E 760 E TF5 6 ON OFF OFF ZX0200 E TF7 7 ON ON ON ZX0300 E TF7 8 ON ON ON ZX0400 E TF7 9 ON ON ON ZX0500 E TF7 A ON ON ON ZX0600 E TF7 A ON ON ON ZX0750 E 760 E TF7 B ON ON ON ZXL0200 E TFD 1 OFF ON ON Notes The settings given in the table are ...

Page 19: ... on diagnostic Display waiting to restart on diagnostic Auto start the unit after 3 minutes Auto Start Check whether evaporator need defrosting Check that return gas service valve is open Check that LP cutout is functioning or is connected to control board 1 second Power On Unit Identification Code Software Version No 3 seconds 3 seconds F With OD Fan Speed Control W O OD Fan Speed Control ZX L ZX...

Page 20: ...Stop the unit Display DLT sensor failure on the diagnostic Display waiting to restart on diagnostic Auto start the unit after 3 minutes Lockout unit if 6 trips in less than 1 hour Display DLT sensor failure lockout on diagnostic Initiate Buzzer Dialer Relay 5 Auto start in 1 Hour Check if liquid sight glass is full If not system must have leakage at somewhere Check whether DLT sensor is connected ...

Page 21: ...y programming procedure INFO Menu Press and release it to access INFO Menu Program Mode below parameter codes or decrease value Maintenance Clock Suction pressure Suction temperature display Condenser pressure Condenser temperature display Enter Alarm Manual Restart Setup Menu ure erature d ser pressu 1 Mid Coil Temp Sensor 2 Suction Pressure Transducer 3 Discharge Temp Sensor ...

Page 22: ...a defined value This is achieved by varying the fan speed The setpoint can be altered using the SEtF parameter Keyboard Press Together for 3 seconds to Lock and unlock keyboard Press together for 3 seconds to enter programming mode Exit programming mode or wait 30 seconds Pre Set Parameters Parameter Value Unit Description SEtC 6 C Evaporation temperature set point SEtF 25 C Fan speed control cond...

Page 23: ...tch alarm ON Mechanical high pressure switch alarm ON Unit is in Alarm status ON There is no new alarm Flashing A new alarm has occurred Icons on LED Display To reset an alarm Press the SET key until rSt is displayed in the lower display To reset all alarms Press and hold the SET key for 10s Refrigerant Setting Press for 3 sec to enter programming mode value will start blinking Use and and to ente...

Page 24: ...ost recent records Press to see that alarm s activation hours To delete alarm press and hold until rSt is showing on lower LED display SEtC value Flashing Press 10 sec to erase alarm Running alarm cannot be erased To Disable Controller During Service Work on ZXD Press for 3 sec or to select parameter parameter value will start blinking or to change set values from On to Off press to memorize new s...

Page 25: ...sage will blink and then flashing End will be shown on the LED After 10sec unit will run with new parameters Remove Hot Key from electronic controller Save Parameters in Hot Key Power on the unit Insert Hot key and press key Factory programmed parameters will be copied to Hot Key uPL message will blink and then flashing End will be shown on the LED Press key and End will stop flashing Power off un...

Page 26: ...ing only Auto reset when LP HAL delta 0 3bar LP E0H Condensing Temperature High Compressors are turned off Fans are turned on Auto reset when Number of activations PEn in PEi time Cond Mid Temp Manual reset when Number of activations PEn in PEi time Press keyfor3secor Turnoff andontheunit Cond Mid F HA HP HAF HFC yes compressor are turned off Auto reset when HAF delta 0 3bar Cond Mid Temp P1 Sucti...

Page 27: ... 4 07 43 4 09 5 37 6 78 8 27 9 80 11 61 12 25 3 29 3 52 3 68 3 80 3 95 4 38 4 39 48 3 55 4 50 6 20 7 57 9 08 10 68 11 23 4 16 4 46 4 49 4 72 4 80 5 07 5 18 ZX05002 27 7 13 8 76 10 44 12 22 14 12 17 28 18 22 2 88 3 03 3 18 3 29 3 47 4 16 4 28 32 6 77 8 31 9 96 11 72 13 68 16 62 17 47 3 37 3 35 3 57 3 67 3 97 4 50 4 58 38 6 24 7 69 9 28 11 06 13 06 15 31 16 34 3 77 3 87 4 07 4 27 4 47 4 98 5 10 43 5...

Page 28: ...0 6 12 7 87 9 70 11 55 5 30 5 33 5 46 5 67 5 95 ZX0500 27 8 55 10 51 12 53 14 66 16 95 3 54 3 72 3 91 4 05 4 27 32 8 12 9 97 11 95 14 06 16 42 4 15 4 13 4 39 4 52 4 88 38 7 49 9 23 11 14 13 28 15 68 4 64 4 76 5 00 5 25 5 49 43 6 53 8 16 10 03 12 18 14 65 5 25 5 25 5 49 5 74 6 10 48 4 75 6 96 9 14 11 39 13 76 6 33 6 40 6 69 6 90 7 13 50 4 04 6 48 8 79 11 07 13 41 6 76 6 87 7 16 7 37 7 55 ZX0600 27 ...

Page 29: ...3 58 3 71 3 85 3 97 4 03 43 3 98 5 00 5 95 6 89 7 83 8 85 3 87 4 00 4 12 4 23 4 33 4 38 ZX050E2 27 7 49 9 05 10 67 12 31 13 93 15 51 3 65 3 73 3 86 4 02 4 25 4 53 32 6 56 8 12 9 76 11 43 13 10 14 74 4 11 4 20 4 32 4 50 4 72 5 00 38 5 56 7 07 8 67 10 32 11 98 13 63 4 59 4 68 4 79 4 96 5 16 5 42 43 4 88 6 28 7 79 9 37 10 98 12 58 5 11 5 17 5 27 5 40 5 59 5 81 ZX060E2 27 8 24 9 72 11 47 13 30 15 69 1...

Page 30: ... 4 35 38 5 90 7 05 8 45 9 95 11 43 12 76 4 32 4 40 4 50 4 62 4 74 4 84 43 5 36 6 43 7 73 9 12 10 49 11 69 4 89 4 95 5 05 5 16 5 27 5 37 ZX050E 27 8 10 9 70 11 55 13 54 15 53 17 38 4 42 4 63 4 86 5 11 5 35 5 57 32 8 05 9 56 11 33 13 21 15 09 16 83 4 59 4 78 4 99 5 22 5 45 5 66 38 7 46 8 86 10 50 12 25 13 99 15 58 5 10 5 27 5 48 5 70 5 93 6 13 43 6 81 8 10 9 63 11 26 12 88 14 33 5 62 5 80 6 01 6 24 ...

Page 31: ... 62 9 49 11 47 13 49 14 40 5 44 5 61 5 80 6 01 6 04 ZXD0600 27 10 41 12 49 14 72 17 66 19 64 20 60 3 70 3 88 4 16 4 50 4 70 4 81 32 9 93 11 71 13 94 16 30 18 87 20 10 4 07 4 25 4 43 4 75 5 29 5 47 38 8 90 10 57 12 85 15 26 17 77 18 92 4 53 4 71 4 90 5 23 5 86 5 98 43 7 60 9 40 11 78 14 26 16 33 17 86 5 17 5 45 5 64 6 10 6 57 6 66 48 9 25 11 15 13 08 15 09 16 06 6 46 6 69 6 96 7 22 7 30 ZXD0750 27 ...

Page 32: ... 07 48 5 32 7 26 8 77 10 50 12 34 6 79 6 88 7 02 7 21 7 43 Notes Based on return gas temperature of 18 3o C at suction superheat of 10 K Power include condenser fan Ambient 38o C and 43o C are typical design conditions for unit selection Capacity and Power kW at 60 Hz TF7 Model Ambient Temperature o C Capacity Evaporating Temperature o C Power Evaporating Temperature o C 20 15 10 5 0 5 20 15 10 5 ...

Page 33: ...4 89 5 81 6 77 7 73 2 88 2 97 3 09 3 21 3 35 3 51 3 68 3 86 4 05 48 1 61 1 90 2 37 2 98 3 71 4 53 3 18 3 28 3 40 3 53 3 68 3 84 ZXL0400 20 3 18 3 85 4 64 5 56 6 60 7 77 9 06 10 48 12 03 1 94 2 08 2 22 2 38 2 54 2 70 2 88 3 06 3 25 27 2 80 3 42 4 16 5 03 6 02 7 14 8 39 9 76 11 26 2 27 2 43 2 59 2 76 2 94 3 12 3 32 3 52 3 73 32 2 58 3 17 3 87 4 71 5 67 6 76 7 97 9 31 10 77 2 58 2 75 2 93 3 11 3 30 3...

Page 34: ...3 45 3 74 4 36 5 22 6 27 3 66 3 68 3 71 3 76 3 82 3 91 48 3 30 3 46 3 72 4 25 5 03 5 98 4 11 4 12 4 13 4 15 4 19 4 25 ZXL0400 20 4 57 4 88 5 55 6 54 7 83 9 39 11 19 13 21 15 43 2 84 2 87 2 96 3 06 3 14 3 19 3 17 3 06 2 83 32 3 61 4 21 5 07 6 17 7 48 8 97 10 62 12 41 14 29 3 25 3 38 3 55 3 72 3 88 3 98 4 01 3 93 3 72 38 3 36 4 02 4 90 5 98 7 22 8 60 10 10 11 68 13 33 3 71 3 88 4 07 4 27 4 45 4 57 4...

Page 35: ...59 6 38 7 29 8 33 3 31 3 40 3 58 3 70 3 91 4 14 4 39 4 66 4 94 48 2 17 2 76 3 33 3 89 4 48 5 12 4 00 4 15 4 30 4 45 4 50 4 60 ZXL040E 20 3 78 4 51 5 38 6 38 7 49 8 71 10 01 11 39 12 84 2 45 2 70 2 75 3 01 3 05 3 12 3 90 4 07 4 20 27 3 24 3 99 4 86 5 85 6 93 8 10 9 35 10 66 12 01 2 69 2 88 3 10 3 34 3 40 3 50 4 10 4 31 4 50 32 3 02 3 77 4 63 5 58 6 63 7 75 8 93 10 16 11 43 2 99 3 17 3 39 3 64 3 90 ...

Page 36: ... 3 27 4 28 5 34 6 42 7 50 3 79 3 92 4 06 4 22 4 39 4 57 48 2 00 2 94 3 92 4 92 5 92 6 89 4 23 4 37 4 53 4 70 4 88 5 07 ZXL040E 3 75 4 74 5 97 7 48 9 27 11 37 13 80 16 58 19 74 2 56 2 76 2 96 3 14 3 30 3 40 3 43 3 37 3 21 32 3 52 4 48 5 60 6 92 8 45 10 21 12 23 14 53 17 12 3 52 3 70 3 91 4 13 4 32 4 49 4 60 4 64 4 60 38 3 50 4 41 5 45 6 65 8 02 9 59 11 37 13 40 15 68 4 07 4 27 4 49 4 73 4 96 5 17 5...

Page 37: ...FJ ZX21KCE PFJ ZX29KCE PFJ Rated Load Ampere R22 Amp R404A R507A 13 2 14 6 16 4 20 0 13 2 14 6 16 4 20 0 LockedRotorAmpere R22 Amp R404A R507A 58 0 61 0 82 0 114 0 58 0 61 0 82 0 114 0 Oil Type R22 R404A R507A MINERAL POE Oil Recharge Volume R22 R404A R507A Liters 1 18 1 33 1 33 1 83 Fan Motor Number of Fan Pieces 1 1 1 1 Diameter mm 450 450 450 450 Fan Speed rpm 933 933 933 933 Air Flow Total m3 ...

Page 38: ...R22 Amp R404A R507A Amp 4 3 5 7 7 4 8 9 11 5 12 0 12 0 5 0 6 1 7 5 9 6 11 5 11 8 11 8 Locked Rotor Ampere R22 Amp R404A R507A Amp 26 0 36 0 44 3 58 6 67 0 101 0 101 0 26 0 36 0 44 3 58 6 67 0 101 0 101 0 Oil Type R22 R404A R507A MINERAL POE Oil Recharge Volume R22 R404A Liters R507A 1 18 1 33 1 83 1 83 1 66 1 66 1 66 FanMotor Number of Fan Pieces 1 1 1 2 2 2 2 Diameter mm 450 450 450 450 450 450 4...

Page 39: ...Load Ampere R22 Amp R404A R507A Amp 8 9 5 11 4 7 5 15 9 3 20 7 10 7 20 7 10 7 25 12 1 8 9 5 1 12 1 7 4 15 7 9 6 24 12 4 23 1 12 6 26 14 1 LockedRotorAmpere R22 Amp R404A R507A Amp 55 27 77 39 115 54 128 64 156 70 164 100 55 27 77 39 115 54 128 64 156 70 164 100 Oil Type R22 R404A R507A MINERAL POE OilRechargeVolume R22 R404A Liters R507A 1 18 1 33 1 83 1 83 1 66 1 66 FanMotor Number of Fan Pieces ...

Page 40: ...TFD ZBD48KQE TFD Rated Load Ampere R22 Amp R404A R507A Amp 7 9 10 10 12 1 12 1 7 7 10 4 9 6 12 4 12 4 LockedRotorAmpere R22 Amp R404A R507A Amp 48 0 64 0 74 0 100 0 100 0 48 0 64 0 74 0 100 0 100 0 Oil Type R22 R404A R507A MINERAL POE OilRechargeVolume R22 R404A Liters R507A 1 24 1 77 1 77 1 77 1 77 Fan Motor Number of Fan Pieces 2 2 2 2 2 Diameter mm 450 450 450 450 450 Fan Speed rpm 830 830 830 ...

Page 41: ...F7 Rated Load Ampere R22 Amp R404A R507A Amp n a n a n a n a 9 6 11 6 12 9 14 6 LockedRotorAmpere R22 Amp R404A R507A Amp n a n a n a n a 54 0 64 0 70 0 78 0 Oil Type R22 R404A R507A n a POE 3MAF OilRechargeVolume R22 R404A Liters R507A 1 24 1 77 1 77 1 77 FanMotor Number of Fan Pieces 2 2 2 2 Diameter mm 450 450 450 450 Fan Speed rpm 933 933 933 933 Air Flow Total m3 h 6966 6966 6966 6966 Total F...

Page 42: ... Load Ampere R22 Amp R404A R507A Amp 5 4 5 5 5 7 7 4 8 1 8 8 11 1 12 1 5 6 6 2 6 0 8 3 8 6 10 0 11 1 14 6 LockedRotorAmpere R22 Amp R404A R507A Amp 39 2 39 2 39 2 51 5 51 5 51 5 74 0 101 0 39 2 39 2 39 2 51 5 51 5 51 5 74 0 101 0 Oil Type R22 R404A R507A MINERAL POE OilRechargeVolume R22 R404A Liters R507A 0 56 0 56 0 56 1 24 1 24 1 24 1 77 1 77 FanMotor Number of Fan Pieces 1 1 1 1 1 2 2 2 Diamet...

Page 43: ...507A Amp 12 1 12 6 12 9 19 1 20 21 4 25 5 28 9 12 1 12 6 12 9 19 1 20 21 4 25 5 28 9 Rated Load Ampere R22 Amp TF7 R404A R507A Amp 5 4 5 5 6 9 7 7 9 9 12 6 14 1 14 4 5 6 6 2 6 9 8 6 9 9 12 6 14 1 14 4 LockedRotorAmpere R22 Amp R404A R507A Amp 73 0 73 0 73 0 110 0 110 0 110 0 186 6 191 0 34 8 34 8 38 6 47 0 66 0 73 5 94 3 94 3 Oil Type R22 R404A R507A MINERAL POE OilRechargeVolume R22 R404A Liters ...

Page 44: ...41 BLUE ZX Condensing Unit Wiring Diagram PFJ 220V 50 Hz 1Ph ATTENTION Unit MUST be grounded ...

Page 45: ...X Platform Condensing Unit 42 5 Only ZXL TF5 has 4 additional posts on the terminal block ZX ZXL Condensing Unit Wiring Diagram TFD 380V 420V 50 Hz 3Ph TF7 380V 60 Hz 3Ph ATTENTION Unit MUST be grounded ...

Page 46: ...43 ZX ZXL Condensing Unit Wiring Diagram TF5 200 230V 50 Hz 60 Hz 3Ph ATTENTION Unit MUST be grounded ...

Page 47: ...it MUST be grounded Notes Dashed line is wired by installer Capacitor1 Black E M1 White White E M2 Black Capacitor2 White White Red Black N N Black 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Compressor DLT Sensor COND Mid Coil Temp Sensor Pressure Transducer HP Switch 25 26 27 28 PWM Valve LP Switch Out 0 10V 4 20mA Hot KeY TTL HP i2F Pb3Pb1Pb2 LP Id3 Id1 1 3 10 12 22 23 24 15 ...

Page 48: ...UST be grounded Notes Dashed line is wired by installer Capacitor1 Black E M1 White White E M2 Black Capacitor2 White White Red Black N N Black 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Compressor DLT Sensor COND Mid Coil Temp Sensor Pressure Transducer HP Switch 25 26 27 28 PWM Valve LP Switch Out 0 10V 4 20mA Hot KeY TTL HP i2F Pb3Pb1Pb2 LP Id3 Id1 12 Brown 6 8 7 4 5 1 3 2 I...

Page 49: ...0 E TFD TF7 20 40 ZXD0750 E TFD TF7 20 40 ZXL ZXL0200 E TFD TF5 TF7 Single Fan 40 80 ZXL0250 E TFD TF5 TF7 40 80 ZXL0300 E TFD TF5 TF7 40 80 ZXL0350 E TFD TF5 TF7 40 80 ZXL0400 E TFD 40 80 ZXL0400 E TF5 TF7 Dual Fan 20 40 ZXL0500 E TFD TF5 TF7 20 40 ZXL0600 E TFD TF5 TF7 20 40 ZXL0750 E TFD TF5 TF7 20 40 Packing Information Conversion Chart Units Conversion Chart KCALH x 3 9683 BTUH WATTS x 3 413 ...

Page 50: ...43 1 34 0 25 1 23 1 83 1 86 1 03 1 67 1 68 0 24 2 81 1 73 2 00 6 0 20 0 0 50 1 44 0 32 1 33 1 96 1 99 1 13 1 79 1 79 0 30 2 98 1 84 2 13 4 0 18 9 0 56 1 54 0 38 1 44 2 09 2 12 1 23 1 91 1 91 0 37 3 15 1 96 2 26 2 0 17 8 0 63 1 66 0 45 1 55 2 22 2 25 1 34 2 03 2 03 0 43 3 32 2 08 2 40 0 0 16 7 0 70 1 77 0 52 1 67 2 36 2 39 1 45 2 17 2 16 0 50 3 50 2 21 2 54 2 0 15 6 0 77 1 89 0 59 1 79 2 50 2 52 1 ...

Page 51: ... 81 13 12 8 28 14 06 15 92 15 72 13 10 15 10 14 58 8 03 21 28 14 36 16 22 98 0 37 8 8 06 13 51 8 57 14 51 16 39 16 18 13 52 15 55 15 01 8 30 21 90 14 78 16 70 100 0 38 9 8 32 13 92 8 86 14 97 16 87 16 66 13 96 16 01 15 45 8 59 22 53 15 20 17 18 102 0 40 0 8 58 14 32 9 15 15 44 17 36 17 14 14 41 16 48 15 90 8 88 23 18 15 63 17 67 104 0 41 1 8 84 14 74 9 46 15 92 17 86 17 63 14 86 16 96 16 35 9 17 2...

Page 52: ...Africa Emerson Climate Technologies PO Box 26382 Jebel Ali Free Zone South Dubai UAE Tel 971 4 811 8100 Fax 971 4 886 5465 Philippines Emerson Climate Technologies 23rd Floor San Miguel Properties Centre 7 St Francis Street Ortigas Center Mandaluyong City Philippines Tel 63 479 3824 Taiwan Emerson Electric Taiwan Co Ltd 3rd Floor Dunhua South Road Section 1 Taipei 10650 Taiwan R O C Tel 886 2 8161...

Reviews: