Note
Mount the instrument bracket with the stamped arrow sign pointing
up. Not following this instruction results in an inadequate mounting
of the instrument.
Figure 4-7: Attaching the instrument bracket and back plate
4.3
Grounding the transmitter
The transmitter operates with the housing either floating or grounded;
however, the extra noise in floating systems affects many types of readout
devices.
If the signal appears either noisy or erratic, grounding the transmitter at a
single point may solve the problem. Grounding of the electronics enclosure
should be done in accordance with both local and national installation
codes.
Quick Start Guide
April 2021
28
Emerson.com/Rosemount