If any number other than 0 is programmed into this parameter user security is applied so that no parameters except Pr
11.44
can be adjusted with the
LED keypad. When this parameter is read via an LED keypad and security is locked it appears as zero. The security code can be modified via serial
comms etc. by setting this parameter to the required value, setting Pr
11.44
to 2 and initiating a reset by setting Pr
10.38
to 100. However security can
only be cleared via the LED keypad.
This parameter defines the drive mode. If this parameter is changed from the current drive mode, Pr
x.00
is set to 1253, 1254, 1255 or 1256, and then
the drive is reset the drive mode is changed to the mode defined by this parameter. After the mode change the default settings of all parameters will
be set according to drive mode. The drive mode will not be changed if the drive is running. If the parameter value is changed and a reset is initiated,
but Pr
x.00
is not equal to 1253, 1254, 1255 or 1256, or the drive is running, this parameter is set back to the value for the current drive mode and the
drive mode is not changed.
This parameter indicates the continuous current rating of the drive for Heavy Duty operation. See section 5.6
Menu 4: Torque and current control
page 88 for more details.
This parameter has four possible values (200, 400, 575, 690) and indicates the voltage rating of the drive.
11.30
User security code
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 to 999
Default
Open-loop, Closed-loop vector, Servo,
Regen
0
Update rate
Background read
11.31
User drive mode
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
1 to 4
Default
Open-loop
Closed-loop vector
Servo
Regen
1
2
3
4
Update rate
Background read
Parameter value
String
Drive mode
1
OPEn LP
Open-loop
2
CL VECt
Closed-loop vector
3
serVO
Servo
4
REGEn
Regen
11.32
Maximum Heavy Duty current rating
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
2
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0.00 to 9999.99 A
Update rate
Write at power-up
11.33
Drive voltage rating
Drive modes
Open-loop, Closed-loop vector, Servo, Regen
Coding
Bit
SP
FI
DE Txt VM DP
ND
RA NC NV PT US RW BU PS
1
1
1
1
1
Range
Open-loop, Closed-loop vector, Servo,
Regen
0 (200) to 3 (690)
Update rate
Write at power-up