4.14.2 Control terminal specification
1
0 V common
Function
Common connection for all external
devices
2
+24 V user output (selectable)
Terminal 2 default function
+24 V user output
Programmability
Can be switched on or off to act as a fourth
digital output (positive logic only) by setting
the source Pr
08.028
and source invert
Pr
08.018
Nominal output current
100 mA
Maximum output current
100 mA
200 mA (total including all Digital I/O)
Protection
Current limit and trip
Sample / update period
2 ms when configured as an output (output
will only change at the update rate of the
source parameter if slower)
3
0 V common
Function
Common connection for all external
devices
4
Digital Output 1
5
Digital Output 2
Terminal 4 default function
AT ZERO SPEED output
Terminal 5 default function
Type
Positive logic voltage source outputs
Input / output mode controlled by... Pr
08.031
, Pr
08.032
Operating as an input
Logic mode controlled by...
Pr
08.029
Absolute maximum applied voltage
range
-3 V to +30 V
Impedance
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k
Ω
Input thresholds
10 V ±0.8 V from IEC 61131-2, type 1
Operating as an output
Nominal maximum output current
100 mA (DIO1 & 2 combined)
Maximum output current
100 mA
200 mA (total including all Digital I/O)
Common to all modes
Voltage range
0 V to +24 V
Sample / Update period
2 ms (output will only change at the update
rate of the source parameter
6
0 V common
Function
Common connection for all external
devices
7
Digital Input 4
8
Digital Input 5
Terminal 7 default function
RUN FORWARD input
Terminal 8 default function
RUN REVERSE input
Type
Negative or positive logic digital inputs
Logic mode controlled by...
Pr
08.029
Voltage range
0 V to +24 V
Absolute maximum applied
voltage range
-3 V to +30 V
Impedance
>2 mA @15 V from IEC 61131-2, type 1,
6.6 k
Ω
Input thresholds
10 V ±0.8 V from IEC 61131-2, type 1
Sample / Update period
250 µs when configured as an input with
destinations Pr
06.035
or Pr
06.036
. 600 µs
when configured as an input with destination
Pr
06.029
. 2 ms in all other cases.
9
+24 V external input
Function
To supply the control circuit
without providing a supply to the
power stage
Programmability
Can be used as a digital input when using
an external 24 Vdc
Sample / Update period
2 ms
Nominal voltage
+24.0 Vdc
Minimum continuous operating
voltage
+19.2 Vdc
Maximum continuous operating
voltage
+30.0 Vdc
Minimum start-up voltage
21.6 Vdc
Recommended power supply
40 W 24 Vdc nominal
Recommended fuse
3 A, 50 Vdc
10
0 V common
Function
Common connection for all external
devices
12
0 V common
Function
Common connection for all external
devices
Summary of Contents for Unidrive M702