TYPE
SERIAL N°
:
:
psi
:
:
:
:
psi
:
1450
gal
lb/s
: DOSAODOR-D Rev. 1
Maximum drive pressure
Maximum operating pressure
Odorant flow range
Control device volume
Specific volume injector N°1
Specific volume injector N°2
TARTARINI
O.M.T.
gal/h
*
*
LEVEL FLOAT AND SWITCH
(kEy 10)
0301520
4008304
0301550
INjECTION RATE
MAXIMUM
OPERATING
PRESSURE
0.13
200 psig /
14.0 bar
0.26
0.53
WARNING MESSAGE
DESCRIPTION
PROBABLE CAUSES
ACTIONS
Supply Tank Warning
The Odorant Supply Tank has reached a
low level. The user sets the volume level
at which the warning will be triggered in
the system configuration data.
1. If the supply tank level is coming in
from the analog input, this can occur
whenever the analog input value is less
than or equal to the low alarm level set
by the user.
2. If the tank level is User Entered, in
other words if the user enters an initial
tank volume, the only time this is
checked is at the end of a fill cycle, as
this should be the only time the volume
of the odorant supply tank changes.
3. “The Current Supply Tank volume”
value is higher than the “Supply Tank
Capacity” value.
1a. Check odorant level in odorant
supply tank.
1b. Check in “System Configuration”
Analog Supply Tank Level Input
Section
: Low Scale Value (Zero)
Odorant Data Configuration Section:
Supply Tank Low Alarm Current
Supply Tank Volume
2a. Check odorant level in odorant
supply tank.
2b. Check in “System Configuration”
Odorant Data Configuration Section:
Supply Tank Capacity Current
Supply Tank Volume
3. Check in “System Configuration”
Odorant Data Configuration Section:
Supply Tank Capacity Current Supply
Tank Volume
Table 4.
Troubleshooting (continued)
26
Type Dosaodor-D