Spence T61 Series Pneumatic 

Temperature Controller

 

 WARNING

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result in an explosion, 

fire and/or chemical contamination 

causing property damage and personal 

injury or death.
Emerson temperature controller must 

be installed, operated and maintained 

in accordance with federal, state and 

local codes, rules and regulations 

and Emerson Process Management 

Regulator Technologies, Inc. 

(Emerson) instructions.
If the temperature controller vents gas 

or a leak develops in the system, service 

to the unit may be required. Failure 

to correct trouble could result in a 

hazardous condition.
Installation, operation and maintenance 

procedures performed by unqualified 

personnel may result in improper 

adjustment and unsafe operation. 

Either condition may result in 

equipment damage or personal injury. 

Only a qualified person shall install 

or service the T61 Series Pneumatic 

Temperature Controllers.

Introduction

Scope of the Manual

This manual provides instructions for installation, 

maintenance and parts information for the T61 Series 

pneumatic temperature controllers.

Product Description

The T61 Series Temperature Controller is ideal for 

wide ranging, fast changing loads on instantaneous 

heaters and other difficult process applications. The 

cascade principle, normally used only on instrument 

type regulators, is the basis for this design.
T61 Series, used with a properly selected A Series 

Pilot or Control Valve, continuously adjusts a 

pressure regulator to the required heater pressure. 

This action, coupled with the fast response of a 

bimetallic thermostat, gives exceptional results. 

Added convenience and economy results from the 

wide (200°F / 93°C) adjustable range and the low air 

consumption (0.35 cfm / 0.59 m

3

/h). These controllers 

have adjustable proportional band as well as over 

temperature protection.

Type T61:

 For applications where air control signal 

decreases as process temperature increases.

Figure 1.

 T61 Series Pneumatic Temperature Controller

Instruction Manual

VCIMD-14960
November 2021

T61 Series

Summary of Contents for Spence T61 Series

Page 1: ... Series Pneumatic Temperature Controllers Introduction Scope of the Manual This manual provides instructions for installation maintenance and parts information for the T61 Series pneumatic temperature controllers Product Description The T61 Series Temperature Controller is ideal for wide ranging fast changing loads on instantaneous heaters and other difficult process applications The cascade princ...

Page 2: ...being held so by initial pressure on the disc and by an internal main spring The pressure pilot is actuated by means of an air signal applied to its diaphragm This signal is received from the temperature pilot as a result of the temperature bulb sensing a drop in temperature from the control setting When steam is turned on it flows through the pressure pilot Figure 3 to No 8B tee Bleedport No 4A r...

Page 3: ...ly physical damage to the controller may result in personal injury or property damage due to escaping of accumulated gas To avoid such injury and damage install the controller in a safe location All pressure equipment should be installed in a non seismic area should not be exposed to fire and should be protected from thunderbolt lightning strikes CAUTION The piping system must be adequately design...

Page 4: ...h the T61 Series controller 4 Gradually turn up temperature adjusting knob until rising loading air pressure causes regulator to open Continue raising temperature setting in this fashion until desired control temperature is reached 5 The T61 Series controller is factory set so that 5 degrees variation above and below the controlled temperature will cause the loading air pressure to vary approximat...

Page 5: ...inspection and replacement of parts depends upon the severity of service conditions or the requirement of local state and federal rules and regulations CAUTION Do not under any circumstances loosen the bolts on the diaphragm chamber of the T61 Series Temperature Controller or attempt to dismantle the thermostat element The system is filled with volatile fluid which if lost will render the pilot in...

Page 6: ...n and move adjusting knob key 4 out to clear stop on dial plate and lock to shaft 3 Unscrew spool key 3 from body by rotating adjusting knob counterclockwise 4 Carefully examine O rings key 6 for nicks and other defects 5 Examine spool key 3 and ball key 2 for defects 6 Clean spool and ball with air pressure 7 Reassemble Testing and Calibrating Reverse Acting For reverse acting pilots control pres...

Page 7: ...WAL05 07927 00 5 Body Set Screw Steel WAL05 11134 00 6 Spool Sealing Rings Viton WAL05 04004 00 7 Sensitivity Screw Steel WAL05 07930 00 8 Valve Spring Stainless steel WAL05 05175 00 9 Pressure Gauge WAL05 17460 00 10 1 8 Nipple Brass WAL05 17459 00 11 1 8 Tee Brass WAL05 17458 00 These parts furnished in Repair Kit Figure 4 T61 Series Assembly TYPE T61 SERIAL NUMBER PLATE AND FLOW ARROW SUPPLY AI...

Page 8: ...ess or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Electric Co does not assume responsibility for the selection use or maintenance of any product ...

Reviews: