![Emerson SolaHD SCM-E-EIP User Manual Download Page 38](http://html.mh-extra.com/html/emerson/solahd-scm-e-eip/solahd-scm-e-eip_user-manual_101913038.webp)
Page: 38
Emerson.com/SolaHD
User Guide
A272-365
4. ROCKWELL ALLEN-BRADLEY SETUP
6/2022
4.3.2 CLASS 3 APPLICATION DATA INTERFACE
Parameter attributes values can be accessed by Class 3 Explicit Message through the ADI Object (0xA2)
with supported services Get_Attribute_Single and Set_Attribute_Single.
ADI Inst. #
Parameter
Data Type
Size
Units
Service
1
SCM| Part
Number
CHAR
16
Get Access only
2
SCM| Serial
Number
UINT32
4
Get Access only
3
SCM|
Manufacturer Lot
Code
UINT32
4
Get Access only
4
SCM|
Manufacturer
Name
CHAR
16
Get Access only
5
SCM| Model
Revision
CHAR
2
Get Access only
6
SCM| Primary
Firmware Rev
UINT8
1
Get Access only
7
SCM| Secondary
Firmware Rev
UINT8
1
Get Access only
8
SCM| Status LED
UINT8
1
See Table 4.3.3
Get Access only
10
SCM| Ambient
Temperature
SINT16
2
0.1°C
Get Access only
101
SDN 1| Product
Name
CHAR
16
Get Access only
102
SDN 1| Serial
Number
CHAR
16
Get Access only
103
SDN 1|
Manufacturer Lot
Code
CHAR
16
Get Access only
104
SDN 1|
Manufacturer
Name
CHAR
16
Get Access only
105
SDN 1| Model
Revision
CHAR
2
Get Access only
106
SDN 1| Primary
Revision
UINT8
1
Get Access only
107
SDN 1|
Secondary
Revision
UINT8
1
Get Access only