Reference Manual
00809-0100-4021, Rev GC
Section 2: Installation
April 2014
Option 3
1.
Ground the sensor wiring shield at the sensor, if possible.
2.
Ensure the sensor wiring and signal wiring shields are electrically isolated from the
transmitter housing and other fixtures that may be grounded.
3.
Ground the signal wiring shield at the power supply end.
Grounded thermocouple inputs
1.
Ground the sensor wiring shield at the sensor.
2.
Ensure the sensor wiring and signal wiring shields are electrically isolated from the
transmitter housing and other fixtures that may be grounded.
3.
Ground the signal wiring shield at the power supply end.
Transmitter housing
Ground the transmitter housing according to local or site electrical requirements. An internal
ground terminal is standard. An optional external ground lug assembly (Option Code G1) can
also be ordered, if needed. Ordering certain hazardous approvals automatically includes an
external ground lug (see
).
A. Sensor Wires
C. 4-20 mA loop
E. DCS
B. Transmitter
D. Shield ground point
A. Sensor Wires
C. 4-20 mA loop
E. DCS
B. Transmitter
D. Shield ground point
A
B
D
C
E
D
A
B
D
C
E
D
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......