Advanced diagnostics availability
Table 9-2:
Diagnostic name
Diagnostic category
Product capability
High Process Noise
Process
Suite 1 (DA1)
Grounding and Wiring Fault
Installation
Suite 1 (DA1)
Coated Electrode Detection
Process
Suite 1 (DA1)
Commanded Meter Verifica-
tion
Meter Health
Suite 2 (DA2)
Continuous Meter Verification
Meter Health
Suite 2 (DA2)
4-20 mA Loop Verification
Installation
Suite 2 (DA2)
Options for accessing Rosemount Magmeter Diagnostics
Rosemount Magmeter Diagnostics can be accessed through the Local Operator Interface
(LOI), a Field Communicator, and AMS
®
Device Manager.
Access diagnostics through the LOI for quicker installation, maintenance, and meter
verification
Rosemount Magmeter Diagnostics are available through the LOI to make maintenance of
every magmeter easier.
Access diagnostics through AMS Device Manager
The value of the diagnostics increases significantly when AMS is used. The user will see
simplified screen flow and procedures on how to respond to the diagnostics messages.
9.2
Licensing and enabling
All advanced diagnostics are licensed by ordering option code DA1, DA2, or both. In the
event that a diagnostic option is not ordered, advanced diagnostics can be licensed in the
field through the use of a license key. Each transmitter has a unique license key specific to
the diagnostic option code. A trial license is also available to enable the advanced
diagnostics. This temporary functionality will be automatically disabled after 30-days or
when power to the transmitter is cycled, whichever occurs first. This trial code can be used
a maximum of three times per transmitter. See the detailed procedures below for entering
the license key and enabling the advanced diagnostics. To obtain a permanent or trial
license key, contact your local Rosemount representative.
9.2.1
Licensing the diagnostics
1.
Power up the transmitter.
2.
Verify the software version is 4.4 software or later.
LOI menu path
Detailed Setup > Device Info > Software Rev
Advanced Diagnostics Configuration
112
Rosemount
®
8732EM Transmitter with HART Protocol Reference Manual
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...