Installation
Field mount transmitter with threaded sensor installation
1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells before
applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell.
3. Seal the nipple and adapter threads with silicone tape.
4. Screw the sensor into the thermowell. Install drain seals if required for severe environments or to
satisfy code requirements.
5. Verify the transmitter failure mode switch is in the desired position.
6. Mount the transmitter-sensor assembly into the thermowell, or remote mount if desired.
7. Seal adapter threads with silicone tape.
8. Pull the field wiring leads through the conduit into the field mount housing. Wire the sensor and
power leads to the transmitter. Avoid contact with other terminals.
9. Install and tighten the covers of two compartments. Enclosure covers must be fully engaged to meet
explosion-proof requirements.
A. Rosemount 644 Field Mount
B. Field mount housing
C. Threaded style sensor
D. Extension
E. Threaded thermowell
Summary of Contents for Rosemount 644 with HART Protocol
Page 2: ......
Page 8: ...vi Reference Manual 00809 0200 4728 Rev SA Title Page July 2018 Title Page ...
Page 48: ...40 Reference Manual 00809 0200 4728 Rev SA Configuration July 2018 Configuration ...
Page 62: ...54 Reference Manual 00809 0200 4728 Rev SA Installation July 2018 Installation ...
Page 111: ......