Reference Manual
00809-0100-4728, Rev MB
Configuration
July 2016
Configuration
Hot Backup configuration with a Field Communicator
The field communicator will walk you through a method to correctly configure the necessary elements
of the Hot Backup feature.
Hot Backup configuration with AMS Device Manager
Right click on the device and select
Configure
.
1. In the left navigation pane choose
Manual Setup
.
2. On the
Diagnostics Tab
find the
Hot Backup
group box.
3. Choose the button “Configure Hot Backup” or “Reset Hot Backup” depending on the desired function
and walk through the guided steps.
4. Click
Apply
when complete.
Hot Backup configuration with Local Operator Interface
To configure Hot Backup on the Local Operator Interface, you will have to Enable the Mode and set the
PV values. Reference
Figure 2-12
below for where to find these in the menu.
Figure 2-12. Configuring Hot Backup with LOI
* Available only if option code (S) is ordered.
** Available only if option Codes (S) and (DC) are both ordered.
For information on using Hot Backup in conjunction with the HART Tri-Loop
™
see
“Using the transmitter
with the HART Tri-Loop” on page 40
.
2.7.4
Sensor Drift Alert configuration
The Sensor Drift Alert command allows the transmitter to set a warning flag (through HART), or go into
analog alarm when the temperature difference between Sensor 1 and Sensor 2 exceeds a user-defined
limit.
This feature is useful when measuring the same process temperature with two sensors, ideally when
using a dual-element sensor. When Sensor Drift Alert mode is enabled, the user sets the maximum
allowable difference, in engineering units, between Sensor 1 and Sensor 2. If this maximum difference is
exceeded, a Sensor Drift Alert warning flag will be set.
From the
HOME
screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 1, 5
CALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
SIMULATE
HART REV
HOT BACK CONFIG**
HOT BACK CONFIG**
DRIFT ALERT**
....
HOT BACK MODE
HOT BACK PV
HOT BACK RESET
BACK TO MENU
EXIT MENU
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Summary of Contents for Rosemount 644 HART
Page 2: ......
Page 16: ...6 Reference Manual 00809 0100 4728 Rev MB Introduction July 2016 Introduction ...
Page 86: ...76 Reference Manual 00809 0100 4728 Rev MB Troubleshooting July 2016 Troubleshooting ...
Page 138: ...128 Reference Manual 00809 0100 4728 Rev MB Index July 2016 Index ...
Page 139: ......