Figure 3-2: Two Different Flange Options are Available
D
A. Service space 550 mm (21.7 in.)
B. Service space 500 mm (19.7 in.)
C. Antenna axis
D. Tank wall
E. Vertical plumb line
F. Tank reference height (R)
G. 30° radar beam
H. Horizontal flange
I. Inclined flange
J. Minimum distance (L) to tank wall
3.2.2
Parabolic antenna requirements
Inclination
The inclination of the Rosemount 5900S with Parabolic Antenna should not exceed 1.5 °
towards the center of the tank. For products with high condensation such as bitumen/
asphalt applications, the radar beam should be directed vertically without any inclination.
Installation
Reference Manual
September 2019
00809-0100-5900
32