4.6
LPG configuration
4.6.1
Preparations
Prerequisites
Before starting configuration of the Rosemount
™
5900S for LPG measurements, ensure
that all mechanical installations are made according to instructions, and all external
sensors such as pressure and temperature sensors are properly connected.
For Rosemount 5900S with F
OUNDATION
™
Fieldbus the LPG Setup is described in
using DeltaV / AMS Device Manager
Highly pressurized vapor above the product surface affects the propagation speed of
microwaves. The Rosemount 5900S level gauge is able to compensate for this, thus
avoiding deviations in measured level due to the vapor.
When the gauge is installed on the empty tank, calibrate the gauge and configure for LPG
measurements.
To install a Rosemount 5900S for LPG measurements perform the following major steps:
Procedure
1. Install the tank and the Rosemount 5900S level gauge in Rosemount TankMaster
WinSetup as described in the Rosemount Tank Gauging
. Ensure that the appropriate tank and device types are selected, and the
temperature and pressure sensors are properly configured. Check that the gauge
communicates with the TankMaster PC.
2. Install the Rosemount 5900S gauge on the still-pipe. Measure the exact distance to
the Verification Pin.
3. Configure the Rosemount 5900S according to the standard procedure for a
Rosemount 5900S level gauge (see the Rosemount Tank Gauging
). Rosemount TankMaster Winsetup is the recommended
configuration tool.
4. Configure the vapor pressure sensor.
5. Set Correction Method to Air Correction Only.
6. Calibrate the Rosemount 5900S.
7. Configure the Verification Pin.
8. Verify position of Verification Pin.
9. Set up the Correction Method that applies to the particular type of product in the
tank.
The LPG installation procedure using Rosemount TankMaster Winsetup is described
in section
.
Configuration
Reference Manual
September 2019
00809-0100-5900
116
Reference Manual
Summary of Contents for Rosemount 5900S Series
Page 1: ...Reference Manual 00809 0100 5900 Rev EA September 2019 Rosemount 5900S Radar Level Gauge ...
Page 6: ...Contents Reference Manual September 2019 00809 0100 5900 vi Reference Manual ...
Page 12: ...Introduction Reference Manual September 2019 00809 0100 5900 12 Reference Manual ...
Page 182: ...Configuration Reference Manual September 2019 00809 0100 5900 182 Reference Manual ...
Page 186: ...Operation Reference Manual September 2019 00809 0100 5900 186 Reference Manual ...
Page 266: ...Product Certifications Reference Manual September 2019 00809 0100 5900 266 Reference Manual ...