14
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
19. If a multidrop connection is desired, each scanner should be linked with a device instance under the
associated virtual serial port. Additionally, the required Datasets should be created. Repeat steps
through
to add each device; choose the appropriate Device Address to match the addresses of
the physical devices.
20. All parameters in DeltaV are now set. To send this configuration to the DeltaV controller,
I/O
under
the expanded controller menu must be right-clicked. Select
Download
->
I/O
to begin the
configuration download.
Note
Anytime a download
to the controller or any of the cards occurs, the 3DMultiVision server will stop communicating
with DeltaV. The server must be restarted or the
SCADA Definition
window must be opened and OK’d to see values on
DeltaV. The SCADA Definition can be found in the 3DVision application under
Tools > Server Options > SCADA
Configuration
. Open the
SCADA Definition
and select
OK
.
Figure 1-5. Download the Configuration
1.4
Using direct connection to DeltaV with a serial card
If a direct connection to a DeltaV serial card is desired, the byte order will need to be manipulated in
DeltaV to see the correct values. The 3D Solids Scanner's byte sending order is high to low; DeltaV
assumes the byte sending order is low to high.
The serial card is one of the card types in the DeltaV Explorer and is therefore configured like any other
card. Each serial card has two ports, and each port can support as many as 16 serial devices.