Reference Manual
00809-0100-4024, Rev CA
Electrical Installation
March 2020
Electrical Installation
Figure 3-2. Schematic Illustration of the Rosemount 5600 Transmitter Connection
3.3
Cables
Depending on local requirements, cable glands, or explosion proof conduits must be used for
connection to the non-intrinsically safe junction box (EEx e). For the connection to the instrinsically safe
junction box (EEx i) use cable glands with integral shield connection for cable diameter 6-12 mm or
conduit.
Use shielded instrument cable 0.5 mm
2
(AWG 20) for analog outputs and serial communication. Use
min. 0.5 mm
2
cable for power supply.
3.4
Power supply
You can use either DC or AC as the built in power supply has a wide input range. The following
specification is valid for the power supply:
24-240 V
DC/AC 0-60 Hz
10 W
15 VA
There is no voltage selector in the electronics compartment since the transmitter power supply unit
automatically adapts to the available voltage within specified limits.
Primary Out
Non-IS
Secondary
output
Primary
output IS
X1
1
2
3
4
1 2 3
4 5 6
7 8 9
X2
6
5
4
3
2
1
7
6.767
Level
m
1 2 3
4 5 6
7 8 9
Junction
box X1
Junction
Box X2
HART
®
interface
X2
1
2
3
4
Optional EEx e
Secondary
output
1 and 2 Not used
Summary of Contents for Rosemount 5600 Series
Page 2: ......
Page 4: ...4 Reference Manual 00809 0100 4024 Rev CA Title Page March 2020 Title Page ...
Page 16: ...16 Reference Manual 00809 0100 4024 Rev CA Introduction March 2020 Introduction ...
Page 125: ...125 Reference Manual 00809 0100 4024 Rev CA Index March 2020 Index Strapping Table 71 ...
Page 126: ...126 Reference Manual 00809 0100 4024 Rev CA Index March 2020 Index ...
Page 127: ......