Using the App Wizard to set-up a flow application
Inputs:
•
Level measurement in feet from transmitter.
•
Open channel is a 60° V-Notch Weir.
•
Maximum flow is 645.50 gallons per minute.
•
Height at maximum flow is 1 ft.
Outputs:
•
Flow rate in gallons per minute.
•
Totalized flow in gallons x 100.
•
2% low flow cut-off.
Getting started