![Emerson Rosemount 3490 Series Reference Manual Download Page 181](http://html.mh-extra.com/html/emerson/rosemount-3490-series/rosemount-3490-series_reference-manual_2400788181.webp)
D
Additional features
D.1
Restoring the factory defaults
To restore the control unit to the factory defaults (erasing all user-entered data):
Prerequisites
Note
The factory defaults may not be the same as the settings when shipped from the factory. It
is advisable to keep a record of settings, if possible.
Procedure
1. If there are HART
®
transmitters connected:
a) Navigate to
SETUP
→
[CONTROLLER]
→
SYSTEM
→
Transmitter Wizard
.
b) Start the Wizard, and use the
Remove
option for each connected
transmitter.
This removal action clears the control unit memory of all transmitter data
that has been uploaded from a HART transmitter, including the Transmitter
Bottom Reference.
2. Navigate to
SETUP
→
[CONTROLLER]
→
SYSTEM
→
DEFAULTS
.
3. Press the
red (enter)
button twice and then wait until “Done”.
4.
Switch off the power to the control unit.
5. If there are two transmitters connected to a Rosemount
™
3492 Control Unit:
a)
Switch off power to the control unit.
b) Remove the second transmitter associated with Transmitter Input Channel 2.
c) Switch on power to the control unit.
6. Put the control unit into
Run App
mode (to automatically find a HART transmitter)
7. If the control unit is a Rosemount 3492 Control Unit:
a)
Switch off power to the control unit.
b) Re-connect the second transmitter.
c) Switch on power to the control unit.
Postrequisites
, to start again.
D.2
Advanced parameter access
The advanced parameter access is selected from the
MAIN MENU
Reference Manual
Additional features
00809-0100-4841
January 2021
Emerson.com/Rosemount
181
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...