Note
For any of the alarms below to be indicated by a relay or current output, an indication
method must be selected.
Related information
Auxiliary functions for relay modes
Set-up alarms
Alarm indication selection
Relay operations alarm
Menu
SETUP
→
[CONTROLLER]
→
APPLICATION
→
ALARM
Table 4-23: Relay Operations Alarm Parameters
Parameter
Description
Factory default
P491
RL operations
It is an alarm condition when the number of
operations done by a selected relay (P492) is higher
than the number in P491.
Relay operation counters parameters D811 to D815
are in the
MONITOR
menu.
0
P492
RL ops rly sel
Select the relay for the monitoring operation
associated with parameter P491.
Disabled
Related information
Auxiliary functions for relay modes
Monitoring the control unit readings
Set-up alarms
Relay run-time alarm
Menu
SETUP
→
[CONTROLLER]
→
APPLICATION
→
ALARM
Table 4-24: Relay Run-time Alarm Parameters
Parameter
Description
Factory default
P493
RL runtime
It is an alarm condition when a relay, selected by
P494, has been energized for longer than the period
(hours and minutes) set by P493.
Run-time counters parameters D821 to D825 are in
the
MONITOR
menu.
0:00 h:m = OFF
P494
RL run rly sel
Select the relay for the monitoring operation
associated with parameter P493.
Disabled
Note
For any of the alarms below to be indicated by a relay or current output, an indication
method must be selected.
Getting started
Reference Manual
January 2021
00809-0100-4841
116
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...