Parameter
Description
drF
Drift failure threshold drF = drA + 5.4 °F (3 °C) . If the temperature
measurement exceeds the deviation value, the temperature transmitter sends
a failure diagnostic message.
Note
•
The drF value is a result of the drA setting. drF cannot be set.
•
Setting drA to OFF automatically results in: drF = 14.4 °F (8 °C)
ddr
Delay of the drift detection. The time which the drift value must be above the
warning threshold drW or alarm threshold drA before the temperature
transmitter sends a diagnostic signal (0.5 - 300 minutes).
drEd
Sets which diagnostic cases the temperature transmitter communicates.
•
ON: Limits the diagnostic cases to "failure" cases.
•
ONdr: Limits the diagnostic cases to "alarm" and "failure" cases.
•
OFF: Limits the diagnostic cases to "warning", "alarm" and "failure" cases.
FOU2
Response of the analog signal when a diagnostic case occurs. Instead of the
measured temperature value, the temperature transmitter provides a defined
current value according to Namur NE43 (On: 21.5 mA; OFF: 3.5 mA).
dOU1
Response of the diagnostic switching output after a diagnostic case occurs.
The output opens, closes, or pulsates depending on the configuration.
P-n
The switching logic for the diagnostic output: pnp or npn.
HI
Displays the highest recorded temperature measurement.
LO
Displays the lowest recorded temperature measurement.
Fnr
Shows the fault number. For more information, see
rES
Restores factory default settings.
Note
Record the current parameter settings before restoring the factory default
settings.
3.2
Operating mode
Eight seconds after applying power, the temperature transmitter is in run mode and is
operating within specifications. In run mode, the transmitter measures and evaluates
temperature and provides output signals according to parameter settings.
Operation
Quick Start Guide
January 2019
00825-0100-4329
18
Quick Start Guide
Summary of Contents for Rosemount 327T
Page 1: ...Quick Start Guide 00825 0100 4329 Rev 01 January 2019 Rosemount 327T Temperature Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4329 4 Quick Start Guide ...
Page 12: ...Introduction Quick Start Guide January 2019 00825 0100 4329 12 Quick Start Guide ...
Page 16: ...Installation Quick Start Guide January 2019 00825 0100 4329 16 Quick Start Guide ...
Page 24: ...Product certifications Quick Start Guide January 2019 00825 0100 4329 24 Quick Start Guide ...