Figure 1-1: Hysteresis function
Figure 1-2: Window function
•
SP: Set point
•
rP: Reset point
•
P: Pressure
•
Hy: Hysteresis
•
Hno: Hysteresis function/normally open
•
Hnc: Hysteresis function/normally closed
•
FE: Window
•
Fno: Window function/normally open
•
Fnc: Window function/normally closed
1.3.2
Analog signal
The transmitter communicates measured pressure using an analog signal.
OU2 defines whether the set measuring range is provided as 4-20 mA (OU2 = I) or as 20-4
mA (OU2 = InEG).
Rerange the transmitter (set new values for ASP and AEP) by either manually entering
range points or with an applied pressure source.
•
Applying a pressure source for the analog start point (tASP) or manually setting the
parameter (ASP) defines the measured value when the analog signal is 4 mA (20 mA at
InEG).
•
Applying a pressure source for the analog end point (tASP) or manually setting the
parameter (ASP) defines the measured value when the output signal is 20 mA (4 mA at
InEG).
Minimum distance between ASP and AEP is 25 percent of the upper range limit (maximum
rangedown 4:1). For pressure range 3A, the minimum distance is 25 percent of the
measuring span.
Introduction
Quick Start Guide
January 2019
00825-0100-4327
8
Quick Start Guide
Summary of Contents for Rosemount 326P
Page 1: ...Quick Start Guide 00825 0100 4327 Rev 01 January 2019 Rosemount 326P Pressure Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4327 4 Quick Start Guide ...
Page 14: ...Installation Quick Start Guide January 2019 00825 0100 4327 14 Quick Start Guide ...
Page 40: ...Setting ranges Quick Start Guide January 2019 00825 0100 4327 40 Quick Start Guide ...
Page 44: ...Product certifications Quick Start Guide January 2019 00825 0100 4327 44 Quick Start Guide ...
Page 47: ...Quick Start Guide 00825 0100 4327 January 2019 Quick Start Guide 47 ...