Appendix F: Programming the 3102 and 3105 using HART
February 2015
Programming the 3102 and 3105 using HART
F.4.7
Distance (D910)
This indicates the distance from the transmitter face to a detected surface.
It is a useful diagnostic because a false surface signal can be identified and related to the physical
nature of the installation.
Note
shows this parameter in a tank geometry illustration.
Field Communicator or AMS Device
Manager
To view the distance to a detected surface
1.
From the
Home
screen, select 3: Service Tools.
2.
Select 1: Alerts.
3.
Select 2: Diagnostic Data.
4.
Select 1: Target Data.
5.
Select 1: Distance D910.
6.
When finished, select EXIT to exit to the previous menu.
Rosemount 3490 Series Control Unit
To view the distance to a detected surface
1.
From the
Main Menu
screen, select MONITOR.
2.
Select the transmitter (e.g. “Tx1: 3102”).
3.
Select DIAGNOSTICS, and then select Distance.
4.
When finished, use the ESC key to exit to the previous menu.
Fast Keys
3, 1, 2, 1, 1
Distance D910
2.327 ft
EXIT
HELP
(
Field Communicator Screen Shown
)
Distance D910
2.227ft
(
Rosemount 3491 Screen Shown
)
Summary of Contents for Rosemount 3101
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4840 Rev CB Title Page February 2015 ...
Page 12: ...x Reference Manual 00809 0100 4840 Rev CB Contents February 2015 Contents ...
Page 34: ...22 Reference Manual 00809 0100 4840 Rev CB Section 3 Installation February 2015 Installation ...
Page 68: ...56 Reference Manual 00809 0100 4840 Rev CB Section 4 Starting up February 2015 Starting up ...
Page 236: ...224 Reference Manual 00809 0100 4840 Rev CB Index February 2015 Index ...
Page 237: ......
Page 238: ......
Page 239: ......