Appendix F: Programming the 3102 and 3105 using HART
February 2015
Programming the 3102 and 3105 using HART
F.2.10
Trim 4 mA / trim 20 mA
This is for calibrating the 4 mA and 20 mA output current from the transmitter. The output
current is temporarily set to 4 mA and 20 mA. Measure the
actual output current
and then input
that mA value to re-calibrate. The output current resumes normal operation after exiting.
Note
The re-calibration procedure is automatically cancelled after 20 minutes of inactivity, and the
previous calibration is restored.
Field Communicator or AMS Device Manager
To re-calibrate the 4 mA and 20 mA
output current
1.
From the
Home
screen, select 3: Service Tools.
2.
Select 4: Maintenance,
3.
Select 1: Analog Calibration.
4.
Select 1: D/A Trim.
5.
Follow the instruction “Connect reference meter”, and then select “OK”.
6.
Input the measured mA from the reference meter, and select “ENTER”.
7.
Select 1: Yes.
8.
Select “OK” to now calibrate the 20 mA output current.
9.
Input the measured mA from the reference meter, and select “ENTER”.
10.
Select 1: Yes. (The output current now returns to normal operation).
Note
When messages appear, take appropriate action if needed and select “OK”.
Fast Keys
3, 4, 1, 1
Analog Calibration
1. D/A Trim
1. D/A Trim
SAVE
HOME
HELP
(
Field Communicator Screen Shown
)
Summary of Contents for Rosemount 3101
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4840 Rev CB Title Page February 2015 ...
Page 12: ...x Reference Manual 00809 0100 4840 Rev CB Contents February 2015 Contents ...
Page 34: ...22 Reference Manual 00809 0100 4840 Rev CB Section 3 Installation February 2015 Installation ...
Page 68: ...56 Reference Manual 00809 0100 4840 Rev CB Section 4 Starting up February 2015 Starting up ...
Page 236: ...224 Reference Manual 00809 0100 4840 Rev CB Index February 2015 Index ...
Page 237: ......
Page 238: ......
Page 239: ......