Reference Manual
00809-0100-4801, Rev FA
October 2010
Rosemount 3051S Series
2-2
CONSIDERATIONS
General
Measurement performance depends upon proper installation of the
transmitter and impulse piping. Mount the transmitter close to the process and
use minimum piping to achieve best performance. Also, consider the need for
easy access, personnel safety, practical field calibration, and a suitable
transmitter environment. Install the transmitter to minimize vibration, shock,
and temperature fluctuation.
IMPORTANT
Install the enclosed pipe plug (found in the box) in the unused conduit
opening. For straight threads, a minimum of 6 threads must be engaged. For
tapered threads, install the plug wrench-tight.
For material compatibility considerations, see document number
00816-0100-3045 on www.rosemount.com.
Mechanical
Steam Service
For steam service or for applications with process temperatures greater than
the limits of the transmitter, do not blow down impulse piping through the
transmitter. Flush lines with the blocking valves closed and refill lines with
water before resuming measurement.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals.
Process leaks could result in death or serious injury.
• Install and tighten all four flange bolts before applying pressure.
• Do not attempt to loosen or remove flange bolts while the transmitter is
in service.
Replacement equipment or spare parts not approved by Rosemount Inc. for use
as spare parts could reduce the pressure retaining capabilities of the transmitter
and may render the instrument dangerous.
• Use only bolts supplied or sold by Rosemount Inc. as spare parts.
Improper assembly of manifolds to traditional flange can damage SuperModule
™
Platform.
• For safe assembly of manifold to traditional flange, bolts must break back
plane of flange web (i.e., bolt hole) but must not contact module housing.
SuperModule and electronics housing must have equivalent approval labeling in
order to maintain hazardous location approvals.
• When upgrading, verify SuperModule and electronics housing certifications are
equivalent. Differences in temperature class ratings may exist, in which case
the complete assembly takes the lowest of the individual component
temperature classes (for example, a T4/T5 rated electronics housing
assembled to a T4 rated SuperModule is a T4 rated transmitter.)
Summary of Contents for Rosemount 3051S Series
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series TOC 6 ...
Page 14: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series 1 4 ...
Page 74: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series 3 32 ...
Page 90: ...Reference Manual 00809 0100 4801 Rev FA October 2010 4 16 Rosemount 3051S Series ...
Page 98: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series 5 8 ...
Page 194: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series A 46 ...
Page 205: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 11 Rosemount 3051S Series ...
Page 206: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 12 ...
Page 207: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 13 Rosemount 3051S Series ...
Page 208: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 14 ...
Page 209: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 15 Rosemount 3051S Series ...
Page 210: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 16 ...
Page 211: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 17 Rosemount 3051S Series ...
Page 212: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 18 ...
Page 213: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 19 Rosemount 3051S Series ...
Page 214: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 20 ...
Page 215: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 21 Rosemount 3051S Series ...
Page 216: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 22 ...
Page 217: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 23 Rosemount 3051S Series ...
Page 218: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 24 ...
Page 219: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 25 Rosemount 3051S Series ...
Page 221: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 27 Rosemount 3051S Series ...
Page 222: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 28 ...
Page 223: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 29 Rosemount 3051S Series ...
Page 224: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 30 ...
Page 225: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 31 Rosemount 3051S Series ...
Page 226: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 32 ...
Page 227: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 33 Rosemount 3051S Series ...
Page 228: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 34 ...
Page 229: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 35 Rosemount 3051S Series ...
Page 230: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 36 ...
Page 231: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 37 Rosemount 3051S Series ...
Page 232: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 38 ...
Page 233: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 39 Rosemount 3051S Series KEMA ...
Page 234: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 40 ...
Page 235: ...Reference Manual 00809 0100 4801 Rev FA October 2010 B 41 Rosemount 3051S Series ...
Page 236: ...Reference Manual 00809 0100 4801 Rev FA October 2010 Rosemount 3051S Series B 42 ...
Page 239: ......