41
Reference Manual
00809-0700-4001, Rev AA
Electrical Installations
May 2017
Electrical Installations
Figure 4-5. Load Limitation
The total resistance load is the sum of the resistance of the signal leads and the load resistance of the
controller, indicator, I.S. Barriers, and related pieces. If intrinsic safety barriers are used, the resistance
and voltage drop must be included.
4.6.3
Wiring the transmitter
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24 AWG or larger
wire and do not exceed 5000 ft (1500 m).
Figure 4-6. 4–20 mA HART
A. DC power supply
B. R
L
≥
250 (necessary for HART communication only)
Perform the following procedure to make wiring connections:
1. Remove the housing cover on terminal compartment side. Do not remove the cover in explosive
atmospheres when the circuit is live. Signal wiring supplies all power to the transmitter.
Maximum loop resistance = 43.5 x (Power supply voltage – 10.5)
The Field Communicator requires a minimum loop resistance of 250
Ω
for communication.
Do not connect the power signal wiring to the test terminals. Incorrect wiring can damage test circuit.
V
Loa
d
(
Ω
s)
Operating
Region
1387
1000
500
0
10.5
20
30
42.4
A
B
Summary of Contents for Rosemount 3051P
Page 2: ......
Page 8: ...6 Reference Manual 00809 0700 4001 Rev AA Contents May 2017 Contents ...
Page 12: ...2 Reference Manual 00809 0700 4001 Rev AA Introduction May 2017 Introduction ...
Page 36: ...26 Reference Manual 00809 0700 4001 Rev AA Configuration May 2017 Configuration ...
Page 74: ...64 Reference Manual 00809 0700 4001 Rev AA Troubleshooting May 2017 Troubleshooting ...
Page 109: ......