33
Reference Manual
00809-0100-2240, Rev DA
October 2017
4.4
Electrical installation
4.4.1
Cable/conduit entries
The electronics housing has three entries for ½ - 14 NPT glands. Optional M20×1.5, minifast and eurofast
adapters are also available.
For remote mounting, the nut and sleeve on the Rosemount 2240S can be replaced with a M32 gland for
connection of temperature sensors/WLS.
Connections must be made in accordance with local or plant electrical codes.
Make sure that unused ports are properly sealed to prevent moisture or other contamination from
entering the terminal block compartment of the electronics housing.
Note
Use the enclosed metal plugs to seal unused ports. The plastic plugs mounted at delivery are not
sufficient as seal!
Note
It is recommended that a sealant of type PTFE is used to prevent water ingress and to enable future
removal of the plug/gland.
Figure 4-1. Cable Entry with NPT Threaded Gland
Ensure that glands for the cable entries meet the following requirements:
IP class 66 and 67
material: metal (recommended)
4.4.2
Power requirements
The Rosemount 2240S temperature transmitter is powered over the Tankbus by the Rosemount 2410
Tank Hub. The Rosemount 2240S has a current consumption of 30 mA.
When installed in a F
OUNDATION
fieldbus system, the Rosemount 2240S is powered by the FF segment.
Note that the NPT threaded gland leaves a
number of threads outside the housing
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......