C.5
Measurement transducer block
The Measurement Transducer block contains the actual measurement data, including temperature,
water level readings, and pressure. Channels 1-10 are assigned to these measurements. The transducer
block includes information about sensor type, engineering units, and all parameters needed to configure
the transmitter.
Table C-6. Measurement Transducer Block Parameters
Index
Number
Parameter
Description
1
ST_REV
The revision level of the static data associated with the
function block. The revision value increments each time a
static parameter value in the block is changed.
2
TAG_DESC
The user description of the intended application of the block.
3
STRATEGY
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
4
ALERT_KEY
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5
MODE_BLK
The actual, target, permitted, and normal modes of the
block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
6
BLOCK_ERR
This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
7
UPDATE_EVT
This alert is generated by any change to the static data.
8
BLOCK_ALM
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The first
alert to become active will set the Active status in the Status
parameter. As soon as the Unreported status is cleared by
the alert reporting task, another block alert may be reported
without clearing the Active status, if the subcode has
changed.
9
TRANSDUCER_DIRECTORY
Directory that specifies the number and starting indices of
the transducers in the transducer block.
10
TRANSDUCER_TYPE
Identifies the transducer.
11
TRANSDUCER_TYPE_VER
12
XD_ERROR
A transducer block alarm subcode. Provides additional error
codes related to transducer blocks.
13
COLLECTION_DIRECTORY
A directory that specifies the number, starting indices, and
DD Item ID’s of the data collections in each transducer within
a transducer block.
14
HOUSING_TEMPERATURE
Temperature inside radar gauge housing
15
TEMPERATURE_UNIT
Measurement unit for temperature
16
WATER_LEVEL
Water level at the bottom of the tank
17
WATER_LEVEL_UNIT
Measurement unit for Water Level
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......