150
October 2017
Reference Manual
00809-0100-2240, Rev DA
B.5 Canada
I6
CSA Intrinsically Safe
Certificate: 3035518C
Standards: CSA-C22.2 No. 157-92 1992 (2012),
CSA-C22.2 No. 1010-1 2004 (2009),
CSA-C22.2 No. 25-1966 1992 (2009),
CSA-C22.2 No. 60529-05 2005 (2010),
CSA-C22.2 No. E60079-0 2011,
CSA-C22.2 No. E60079-11 2011,
CSA-C22.2 No. 94 2011
Markings:
IS / I,II,III / 1 / ABCDEFG / T4 Ta = -50°C to 70°C;
9240040-910 Entity/FISCO; Type 4X/IP66/IP67
I / 0 / Ex ia IIC / T4 Ta = -50°C to 70°C; -
9240040-910 Entity/FISCO; Type 4X/IP66/IP67
I / 1 / Ex ib [ia] IIC T4 Ta = -50°C to 70°C
9240040-910 FISCO; Type 4X/IP66/IP67
Special Conditions for Safe Use (X):
1. The enclosure contains aluminum and is considered to
present a potential risk of ignition by impact or friction.
2. Rating I / 1 / Ex ib [ia] IIC T4 Ta = -50°C to 70°C 9240040-910
FISCO; Type 4X/IP66/IP67 is only applicable when supplied
from an FM certified Ex [ib] FISCO Power Supply with
triplicate output voltage limitation meeting the
requirements for two faults ("ia" voltage limitation).
3. The Rosemount 2240S
Multi-Input Temperature Transmitter
will not pass the 500Vrms dielectric strength test and this
must be taken into account during installation
B.6 Europe
I1
ATEX Intrinsic Safety
Certificate: FM09ATEX0047X
Standards: EN 60079-0:2012,
EN 60079-11:2012,
EN 60079-26:2007,
EN 60529:2013
Markings:
FISCO Field Device
II 1 G Ex ia IIC T4 Ta = -50°C to 70°C Entity/FISCO; IP66, IP67
II 2(1) G Ex ib [ia] IIC T4 Ta = -50°C to 70°C FISCO; IP66, IP67
Special Conditions for Safe Use (X):
1. The enclosure contain aluminum and is considered to
present a potential risk of ignition by impact or friction. Care
must be taken during installation and use to prevent impact
or friction.
2. Rating II 2(1) G Ex ib [ia] IIC T4 Ta = -50°C to 70°C FISCO
9240040-976; IP66, IP67 is only applicable when supplied
from a certified Ex [ib] FISCO Power Supply with triplicate
output voltage limitation meeting the requirements for two
faults ("ia" voltage limitation).
3. The Rosemount 2240S
Multi-input Temperature Transmitter
will not pass the 500Vrms dielectric strength test and this
must be taken into account during installation.
Ui
Ii
Pi
Ci
Li
Entity parameters
30 V
300 mA
1.3 W
2.2 nF
2 μH
FISCO parameters
17.5V
380 mA
5.32 W
2.2 nF
2 μH
Ui
Ii
Pi
Ci
Li
Entity parameters
30 V
300 mA
1.3 W
2.2 nF
2 μH
FISCO parameters
17.5V
380 mA
5.32 W
2.2 nF
2 μH
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......