background image

18

Reference Manual

00809-0300-4410, Rev BA

Configuration

January 2018

Configuration

The transmitter automatically and continuously performs self-diagnostic routines. If the self-diagnostic 
routines detect a failure, the transmitter drives the output to configured alarm and value based on the 
position of the alarm switch. Se

“Setting transmitter alarm” on page 39

.

Table 2-4.  Rosemount Alarm and Saturation Values

Table 2-5.  NAMUR-Compliant Alarm and Saturation Values

Table 2-6.  Custom Alarm and Saturation Values

Failure mode alarm and saturation levels can be configured using a Field Communicator, AMS Device 
Manager, and the LOI. The following limitations exist for custom levels:

Low alarm level must be less than the low saturation level

High alarm level must be higher than the high saturation level

Alarm and saturation levels must be separated by at least 0.1 mA 

The configuration tool will provide an error message if the configuration rule is violated.

Note

Transmitters set to HART multidrop mode send all saturation and alarm information digitally; saturation 
and alarm conditions will not affect the analog output. See also 

“Establishing multidrop 

communication” on page 24

.

Field Communicator

AMS Device Manager

1. Right click on the device, and select 

Configure

.

2. Select 

Configure Alarm and Saturation Levels

 button.

3. Follow screen prompts to configure alarm and saturation levels.

LOI

Refer to 

Figure 2-13

 for instructions to configure alarm and saturation levels.

Level

4–20 mA saturation

4–20 mA alarm

Low

3.90 mA

 3.75 mA

High

20.80 mA

 21.75 mA 

Level

4–20 mA saturation

4–20 mA alarm

Low

3.80 mA 

 3.60 mA

High

20.50 mA 

22.50 mA

Level

4–20 mA saturation

4–20 mA alarm

Low

3.70 mA– 3.90 mA

3.60–3.80 mA

High

20.10 mA –22.90 mA

20.20 mA – 23.00 mA

From the 

HOME

 screen, enter the Fast Key sequence 

 Device Dashboard Fast Keys

2, 2, 2, 5

Summary of Contents for Rosemount 2051G

Page 1: ...Reference Manual 00809 0400 4101 Rev BA January 2018 Rosemount 2051G In Line Pressure Transmitter with HART Revision 5 and 7 Selectable Protocol ...

Page 2: ......

Page 3: ...onfiguration basics 9 2 6 1 Configuring on the bench 9 2 6 2 Configuration tools 10 2 6 3 Setting the loop to manual 11 2 7 Verify configuration 11 2 7 1 Field Communicator 11 2 7 2 AMS Device Manager 12 2 7 3 Local operator interface 12 2 8 Verifying process variables configuration 12 2 8 1 Field Communicator 12 2 8 2 AMS Device Manager 12 2 9 Basic setup of the transmitter 13 2 9 1 Setting press...

Page 4: ...anical considerations 29 3 4 Installation procedures 29 3 4 1 Mount the transmitter 29 3 4 2 Impulse piping 31 3 4 3 Inline process connection 33 3 5 Rosemount 306 Manifold 34 3 5 1 Rosemount 306 Integral Manifold installation procedure 34 4Section 4 Electrical Installation 4 1 Overview 35 4 2 Safety messages 35 4 3 Local Operating Interface LOI LCD display 36 4 3 1 Rotating LCD LOI display 36 4 4...

Page 5: ...tory trim sensor trim 51 5 6 Trim the analog output 51 5 6 1 Performing digital to analog trim 4 20mA output trim 52 5 6 2 Performing digital to analog trim 4 20mA output trim using other scale 53 5 6 3 Recalling factory trim analog output 53 5 7 Switching HART revision 54 5 7 1 Generic menu 54 5 7 2 Field Communicator 54 5 7 3 AMS Device Manager 55 5 7 4 LOI 55 6Section 6 Troubleshooting 6 1 Over...

Page 6: ...7 5 1 Proof test 67 7 5 2 Partial proof test 67 7 5 3 Comprehensive proof test 67 7 6 Inspection 68 7 6 1 Visual inspection 68 7 6 2 Special tools 68 7 6 3 Product repair 68 7 6 4 Rosemount 2051G SIS reference 68 7 6 5 Failure rate data 68 7 6 6 Failure values 68 7 6 7 Product life 68 AAppendix A Reference Data A 1 Product Certifications 69 A 2 Ordering Information Specifications and Drawings 69 B...

Page 7: ...and order related questions United States 1 800 999 9307 7 00 am to 7 00 pm CST Asia Pacific 65 777 8211 Europe Middle East Africa 49 8153 9390 North American Response Center Equipment service needs 1 800 654 7768 24 hours includes Canada Outside of these areas contact your local Emerson representative The products described in this document are NOT designed for nuclear qualified applications Usin...

Page 8: ...safe installation Before connecting a Field Communicator in an explosive atmosphere ensure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an explosion proof flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death Install and tighten proc...

Page 9: ...e most common operating problems Section 7 Safety Instrumented Systems Requirements provides identification installation configuration operation and maintenance and inspection information for Safety Instrumented Systems Appendix A Reference Data supplies reference and specification data as well as ordering information Appendix B Field Communicator Menu Trees and Fast Keys contains intrinsic safety...

Page 10: ...2 Reference Manual 00809 0400 4101 Rev BA Introduction January 2018 Introduction ...

Page 11: ...tter page 13 Configuring the LCD display page 17 Detailed transmitter setup page 17 Performing transmitter tests page 21 Configuring burst mode page 23 Establishing multidrop communication page 24 2 1 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety is...

Page 12: ...ed with a safe installation Before connecting a Field Communicator in an explosive atmosphere ensure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an explosion proof flameproof installation do not remove the transmitter covers when power is applied to the unit Electrical shock can result in death or serious injury Avoid c...

Page 13: ...configuration tool Value shown is minimum revision that could correspond to NAMUR revisions HART universal revision Device revision 3 3 Device driver file names use device and DD revision e g 10_01 HART Protocol is designed to enable legacy device driver revisions to continue to communicate with new HART devices To access new functionality the new device driver must be downloaded It is recommended...

Page 14: ...e 13 Select Linear Output page 13 Set Damping page 16 Verify Apply Pressure Yes Within Specifications Yes No Refer to Section 5 Operation and Maintenance Configure Security and Alarm page 36 Mount Transmitter page 29 Wire Transmitter page 41 Power Transmitter page 40 Trim the Transmitter page 48 Done Review Transmitter Configuration page 9 Confirm Transmitter Configuration page 11 Configure for Pr...

Page 15: ...ng diaphragm the oil deflects the sensor which then changes its capacitance or voltage signal This signal is then changed to a digital signal by the Signal Processing The microprocessor then takes the signals from the Signal Processing and calculates the correct output of the transmitter This signal is then sent to the D A converter which converts the signal back to the analog signal then superimp...

Page 16: ...nsor module electronics B 4 20 mA signal to control system C Field communicator A B C Signal Processing Temp Sensor Sensor Module Memory Microprocessor Sensor linearization Rerange Damping Diagnostics Engineering units Communication Memory Configuration Digital to Analog Signal Conversion Digital Communication Pressure Sensor ...

Page 17: ... after installation Configuring the transmitter on the bench using either a Field Communicator AMS Device Manager or LOI ensures all transmitter components are in working order prior to installation Verify that the security switch is set in the unlock position in order to proceed with configuration See Figure 4 2 on page 37 for switch location 2 6 1 Configuring on the bench To configure on the ben...

Page 18: ...vice Manager requires loading the most current Device Descriptor DD for this device Download the latest DD at Emerson com or FieldCommGroup org Note All steps using AMS Device Manager will be described using version 11 5 Configuring with a local operator interface The LOI requires option code M4 to be ordered To activate the LOI push either configuration button Configuration buttons are located on...

Page 19: ...the loop to manual control as a separate operation 2 7 Verify configuration It is recommended that various configuration parameters are verified prior to installation into the process The various parameters are detailed out for each configuration tool Depending on what configuration tool s are available follow the steps listed relevant to each tool 2 7 1 Field Communicator Configuration parameters...

Page 20: ...his section describes how to verify that the correct process variables are selected 2 8 1 Field Communicator 2 8 2 AMS Device Manager 1 Right click the device and select Overview from the menu 2 Select the All Variables button to display the primary secondary tertiary and quaternary variables From the HOME screen enter the Fast Key sequences listed Function Fast Key sequence HART 7 HART 5 Alarm an...

Page 21: ...The range values command sets each of the lower and upper range analog values to a pressure The lower range point represents 0 percent of range and the upper range point represents 100 percent of range In practice the transmitter range values may be changed as often as necessary to reflect changing process requirements For a complete listing of Range and Sensor limits refer to Ordering Information...

Page 22: ...ssure source Reranging using an applied pressure source is a way of reranging the transmitter without entering specific 4 and 20 mA points Field Communicator AMS Device Manager 1 Right click the device select Configure 2 Select the Analog Output tab 3 Select Range by Applying Pressure button and follow the screen prompts range the transmitter LOI Use Figure 2 9 to manually rerange the device using...

Page 23: ...ons 2 Confirm device has local zero and span buttons by verifying blue retainer under the tag 3 Apply transmitter pressure 4 Rerange the transmitter a To change the zero 4 mA while maintaining the span press and hold zero button for at least two seconds then release b To change the span 20 mA while maintaining the zero point press and hold the span button for at least two seconds and then release ...

Page 24: ... response time of the transmitter higher values can smooth variations in output readings caused by rapid input changes Determine the appropriate damping setting based on the necessary response time signal stability and other requirements of the loop dynamics within your system The damping command utilizes floating point configuration allowing the user to input any damping value within 0 0 60 0 sec...

Page 25: ...p select the Display tab 3 Select desired display options and click Send LOI Refer to Figure 2 12 for LCD display configuration using a LOI Figure 2 12 Display with LOI 2 11 Detailed transmitter setup 2 11 1 Configuring alarm and saturation levels In normal operation the transmitter will drive the output in response to pressure from the lower to upper saturation points If the pressure goes outside...

Page 26: ...uration levels must be separated by at least 0 1 mA The configuration tool will provide an error message if the configuration rule is violated Note Transmitters set to HART multidrop mode send all saturation and alarm information digitally saturation and alarm conditions will not affect the analog output See also Establishing multidrop communication on page 24 Field Communicator AMS Device Manager...

Page 27: ... Variable value position 1 Custom unit equivalent to the lower known value point Pressure value position 2 Upper known value point Scaled Variable value position 2 Custom unit equivalent to the upper known value point Linear offset The value required to zero out pressures effecting the desired pressure reading Field Communicator 1 Follow the screen prompts to configure scaled variable a Select Lin...

Page 28: ...riables only apply if HART burst mode is being used Field Communicator AMS Device Manager 1 Right click the device and select Configure 2 Select Manual Setup and click on the HART tab 3 Assign Primary secondary tertiary and quaternary variables under Variable Mapping 4 Select Send 5 Carefully read the warning and select Yes if it is safe to apply the changes LOI Refer to Figure 2 15 for instructio...

Page 29: ... on page 11 2 12 2 Performing an analog loop test The analog loop test command verifies the output of the transmitter the integrity of the loop and the operations of any recorders or similar devices installed in the loop It is recommended that the 4 20 mA points in addition to alarm levels when installing repairing or replacing a transmitter The host system may provide a current measurement for th...

Page 30: ...2 12 3 Simulate device variables It is possible to temporarily set the Pressure Sensor Temperature or Scaled Variable to a user defined fixed value for testing purposes Once the simulated variable method is left the process variable will be automatically returned to a live measurement Simulate device variables is only available in HART Revision 7 mode Field Communicator AMS Device Manager 1 Right ...

Page 31: ...nt Access to information other than dynamic transmitter data is obtained through the normal poll response method of HART communication A Field Communicator AMS Device Manager or the control system may request any of the information that is normally available while the transmitter is in burst mode Between each message sent by the transmitter a short pause allows the Field Communicator AMS Device Ma...

Page 32: ...que address and responds to the commands defined in the HART protocol Field Communicators and AMS Device Manager can test configure and format a multidropped transmitter the same way as a transmitter in a standard point to point installation Figure 2 17 shows a typical multidrop network This figure is not intended as an installation diagram Figure 2 17 Typical Multidrop Network 4 20 mA only A HART...

Page 33: ...x enter polling address in the Polling Address box select Send 3 In HART Revision 7 mode a Select Manual Setup select the HART tab and select the Change Polling Address button 4 Carefully read the warning and click Yes if it is safe to apply the changes 2 14 2 Communicating with a multidropped transmitter To communicate with a multidrop transmitter the Field Communicator or AMS Device Manager has ...

Page 34: ...26 Reference Manual 00809 0300 4410 Rev BA Configuration January 2018 Configuration ...

Page 35: ...scribe recommended pipe fitting and wiring procedures for initial installation Dimensional drawings for each transmitter variation and mounting configuration are included on page 29 Note For transmitter disassembly and reassembly refer to Disassembly procedures on page 61 and Reassembly procedures on page 62 3 2 Safety messages Procedures and instructions in this section may require special precau...

Page 36: ...ons associated with a safe installation Before connecting a Field Communicator in an explosive atmosphere ensure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an explosion proof flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death In...

Page 37: ...out using an additional mounting bracket When this is not desirable mount directly to a wall panel or two inch pipe using the optional mounting bracket see Figure 3 1 on page 30 For dimensional drawing information refer to Appendix A Reference Data on page 69 Note Most transmitters are calibrated in the upright position Mounting the transmitter in any other position will shift the zero point to th...

Page 38: ... 156 2 81 71 4 78 121 6 90 175 2 in U Bolt for pipe mounting clamp shown 1 42 36 2 81 71 5 16 1 Bolts for panel mounting not supplied 1 4 11 4 Bolts for transmitter mounting not supplied 3 85 98 5 13 130 4 26 109 1 4 11 4 Bolts for transmitter mounting not supplied 1 42 36 Carbon Steel CS Head Markings B7M 316 B8M F593_ Stainless steel SST head markings KM 660 CL A Alloy K 500 head marking The las...

Page 39: ...nt drain vent valve upward to allow gases to vent Gas measurement Place tap in the top or side of the line Mount the transmitter beside or above the tap so liquid will drain into the process line Steam measurement Place tap to the side of the line Mount the transmitter below the taps to ensure that the impulse piping will stay filled with condensate In steam service above 250 F 121 C fill impulse ...

Page 40: ...iquid in a gas line and density variations between the legs The best location for the transmitter in relation to the process pipe is dependent on the process Use the following guidelines to determine transmitter location and placement of impulse piping Keep impulse piping as short as possible For liquid service slope the impulse piping at least 1 in ft 8 cm m upward from the transmitter toward the...

Page 41: ...e low side pressure port on the inline gage transmitter is located in the neck of the transmitter behind the housing The vent path is 360 degrees around the transmitter between the housing and sensor See Figure 3 6 Keep the vent path free of any obstruction such as paint dust and lubrication by mounting the transmitter so the process can drain away Figure 3 6 In Line Gage Low Side Pressure Port A ...

Page 42: ...ral Manifold is used with the Rosemount 2051G In Line Transmitter to provide block and bleed valve capabilities of up to 10000 psi 690 bar Figure 3 7 Rosemount 2051G and 306 In line Manifold 3 5 1 Rosemount 306 Integral Manifold installation procedure Assemble the Rosemount 306 Manifold to the Rosemount 2051G In Line Transmitter with a thread sealant ...

Page 43: ...ons in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Refer to the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Installation of this transmitter in an explosive environme...

Page 44: ...LOI display B Extended cover C Captive screws 4 3 1 Rotating LCD LOI display 1 Secure the loop to manual control and remove power to transmitter 2 Remove transmitter housing cover 3 Remove screws form the LCD LOI display and rotate to desired orientation a Insert 10 pin connector into the display board for the correct orientation Carefully align pins for insertion into the output board 4 Re insert...

Page 45: ...itch Follow the steps below to enable the security switch 1 Set loop to manual and remove power 2 Remove transmitter housing cover 3 Use a small screwdriver to slide the switch to the lock position 4 Replace transmitter housing cover cover must be fully engaged to comply with explosion proof requirements 4 4 2 HART lock The HART Lock prevents changes to the transmitter configuration from all sourc...

Page 46: ...uration Buttons dropdown menu select Disabled to lock external local keys 4 Select Send 5 Confirm service reason and click Yes 4 4 4 LOI password A Local Operator Interface Password can be entered and enabled to prevent review and modification of device configuration via the LOI This does not prevent configuration from HART or external keys analog zero and span Digital zero trim The LOI password i...

Page 47: ...e power 2 Remove transmitter housing cover 3 Use a small screwdriver to slide switch to desired position 4 Replace transmitter cover cover must be fully engaged to comply with explosion proof requirements 4 6 Electrical considerations Note Make sure all electrical installation is in accordance with national and local code requirements Do not run signal wiring in conduit or open trays with power wi...

Page 48: ...uired for loops with a 250 Ω resistance Note A minimum loop resistance of 250 Ωs is required to communicate with a Field Communicator If a single power supply is used to power more than one transmitter the power supply used and circuitry common to the transmitters should not have more that 20 Ωs of impedance at 1200 Hz If all connections are not sealed excess moisture accumulation can damage the t...

Page 49: ... use 24 AWG or larger wire and do not exceed 5000 ft 1500 m Figure 4 6 4 20 mA HART A DC power supply B R L 250 necessary for HART communication only Perform the following procedure to make wiring connections 1 Remove the housing cover on terminal compartment side Do not remove the cover in explosive atmospheres when the circuit is live Signal wiring supplies all power to the transmitter Maximum l...

Page 50: ... drain wire must be trimmed and insulated ensuring that the signal cable shield and drain wire do not come in contact with the transmitter case See Transmitter case grounding on page 43 for instructions on grounding the transmitter case Follow the steps below to correctly ground the signal cable shield 1 Remove the field terminals housing cover 2 Connect the signal wire pair at the field terminals...

Page 51: ...Figure 4 8 on page 43 This connection is only available with option T1 Figure 4 8 Internal Ground Connection A Internal ground location B External ground location C Positive D Negative E Test Note Grounding the transmitter case via threaded conduit connection may not provide sufficient ground continuity Transient protection terminal block grounding The transmitter can withstand electrical transien...

Page 52: ...allations Figure 4 9 Transient Protection Terminal Block A Lightning bolt location Note The transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded Use the guidelines to ground the transmitter case Refer to Figure 4 8 on page 43 A ...

Page 53: ...ollowing safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Review the approvals section of the reference manual for any restrictions associated with a safe insta...

Page 54: ...eet plant requirements or industry standards Complete calibration of the transmitter can be split into two halves Sensor Calibration and Analog Output Calibration Sensor calibration allows the user to adjust the pressure digital value reported by the transmitter to be equal to a pressure standard The sensor calibration can adjust the pressure offset to correct for mounting conditions or line press...

Page 55: ...rim on page 49 3 Check reported analog output against the live analog output If they do not match perform an analog output trim See Performing digital to analog trim 4 20mA output trim on page 52 Trimming with configuration buttons Local configuration buttons are external buttons located underneath the top tag of the transmitter There are two possible sets of local configuration buttons that can b...

Page 56: ...ility per month Step 5 Calculate calibration frequency 5 5 Trim the pressure signal 5 5 1 Sensor trim overview A sensor trim corrects the pressure offset and pressure range to match a pressure standard The upper sensor trim corrects the pressure range and the lower sensor trim zero trim corrects the pressure offset An accurate pressure standard is required for full calibration A zero trim can be p...

Page 57: ...per and lower sensor trim is a two point sensor calibration where two end point pressures are applied all output is linearized between them and requires an accurate pressure source Always adjust the low trim value first to establish the correct offset Adjustment of the high trim value provides a slope correction to the characterization curve based on the low trim value The trim values help optimiz...

Page 58: ...ce and under the Method drop down menu move cursor over Calibrate and under Sensor Trim and select Upper Sensor Trim LOI Perform an upper and lower Sensor trim by referencing Figure 5 3 Figure 5 3 Sensor Trim with LOI Performing a digital zero trim option DZ A digital zero trim option DZ provides the same function as a zero lower sensor trim but can be completed in hazardous areas at any given tim...

Page 59: ...ual 3 Select Next 4 Select Sensor Trim under Trim to recall and click Next 5 Follow the screen prompts to recall sensor trim LOI Refer to Figure 5 4 to recall factory sensor trim Figure 5 4 Recall Factory Trim Sensor Trim with LOI 5 6 Trim the analog output The Analog Output Trim commands allow you to adjust the transmitter s current output at the 4 and 20 mA points to match the plant standards Th...

Page 60: ... the transmitter to a 20 mA output with additional loop resistance Refer to Power supply on page 40 Field Communicator From the HOME screen enter the Fast Key sequence and follow the steps within the Field Communicator to complete the 4 20 mA output trim AMS Device Manager Right click the device and under the Method drop down menu move cursor over Calibrate and select Analog Calibration 1 Select D...

Page 61: ...ight click the device and under the Method drop down menu move cursor over Calibrate and select Analog Calibration 2 Select Scaled Digital to Analog Trim 3 Follow screen prompts to perform a 4 20mA output trim 5 6 3 Recalling factory trim analog output The Recall Factory Trim Analog Output command allows the restoration of the as shipped factory settings of the analog output trim This command can ...

Page 62: ... Revision 7 device it should load a generic menu with limited capability The following procedures allow for switching between HART Revision 7 and HART Revision 5 from a generic menu 1 Locate Message field a To change to HART Revision 5 Enter HART5 in the message field b To change to HART Revision 7 Enter HART7 in the message field 5 7 2 Field Communicator From the HOME screen enter the Fast Key se...

Page 63: ... or greater are compatible with HART Revision 7 5 7 4 LOI Navigate to HART REV within the extended menu and select either HART REV 5 or HART REV 7 Use Figure 5 8 below to change HART Revision Figure 5 8 Change HART Revision with LOI EXTENDED MENU CALIBRAT DAMPING TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMULATE HART REV HART REV BACK TO MENU EXIT MENU VIEW CONFIG ZERO ...

Page 64: ...56 Reference Manual 00809 0400 4101 Rev BA Operation and Maintenance January 2018 Operation and Maintenance ...

Page 65: ... the following safety messages before performing an operation preceded by this symbol Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Review the approvals section of the Rosemount 2051G Reference Manual for any restrictions associ...

Page 66: ...n alarm condition Perform analog trim Check that power wires are connected to the correct signal terminals positive to positive negative to negative and not the test terminal Transmitter will not respond to changes in applied pressure Check impulse piping or manifold for blockage Verify applied pressure is between the 4 and 20 mA points Verify the output is not in alarm condition Verify transmitte...

Page 67: ... all parameters listed in Device Information 2 Perform a Device Reset 3 Replace Pressure Transmitter Critical Electronics Data Error Auserwrittenparameterdoesnot match the expected value 1 Confirm and correct all parameters listed in Device Information 2 Perform a Device Reset 3 Replace pressure transmitter Sensor Failure FAIL SENSOR FAIL SENSOR A failure has been detected in the pressure sensor 1...

Page 68: ...screen LOI screen Problem Recommended action Non Critical User Data Warning MEMRY WARN MEMORY WARN A user written parameter does not match expected value 1 Confirm and correct all parameters listed in Device Information 2 Perform a Device Reset 3 Replace the pressure transmitter Sensor Parameter Warning A user written parameter does not match expected value 1 Confirm and correct all parameters lis...

Page 69: ...rtment labeled FIELD TERMINALS Analog Output Fixed ANLOG FIXED ANALOG FIXED The analog output is fixed and does not represent the process measurement This may be caused by other conditions in the device or because the device has been set to loop test or multidrop mode 1 Take action on any other notifications from the device 2 If the device is in loop test and should no longer be disable or momenta...

Page 70: ...l directly backwards so to not bend or damage the connection pins on the electronics board Note Ensure not to attempt to pull out the electronics board from the housing as this could permanently damage the transmitter 6 5 Reassembly procedures 6 5 1 Installing LOI LCD display 1 While aligning the captive screws with the respective holes on the electronics board connect the LCD LOI display to the e...

Page 71: ...t Emerson representative Emerson Instrument and Valve Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard The product being returned will require a copy of the required Safety...

Page 72: ...64 Reference Manual 00809 0400 4101 Rev BA Troubleshooting January 2018 Troubleshooting ...

Page 73: ...ification All Rosemount 2051G Transmitters must be identified as safety certified before installing into SIS systems To identify a safety certified Rosemount 2051G 1 Check Namur Software Revision located on the metal device tag SW _ _ _ 2 Verify that option code QT is included in the transmitter model code 7 3 Installation in SIS applications Installations are to be performed by qualified personne...

Page 74: ...ess The damping value response time must not exceed the loop requirements Reference Damping on page 16 to change damping value 7 4 2 Alarm and saturation levels DCS or safety logic solver should be configured to match transmitter configuration Figure 7 1 identifies the three alarm levels available and their operation values Figure 7 1 Alarm Levels Rosemount alarm level Namur alarm level Custom ala...

Page 75: ...and to the transmitter to go to the low alarm current output and verify that the analog current reaches that value 2 6 Remove the bypass and otherwise restore the normal operation 7 Place the Security switch in the position 7 5 3 Comprehensive proof test The comprehensive proof test consists of performing the same steps as the simple suggested proof test but with a two point calibration of the pre...

Page 76: ...unt Report A Failure All product repair and part replacement should be performed by qualified personnel 7 6 4 Rosemount 2051G SIS reference The Rosemount 2051G must be operated in accordance to the functional and performance specifications provided in Specifications and Reference Data on page 69 7 6 5 Failure rate data The FMEDA report includes failure rates The report is available under Certifica...

Page 77: ...he green menu bar and click Documents Drawings 3 Click Manuals Guides 4 Select the appropriate Quick Start Guide A 2 Ordering Information Specifications and Drawings To view current Rosemount 2051G In Line Pressure Transmitter Ordering Information Specifications and Drawings follow these steps 1 Go to Emerson com Rosemount Rosemount 2051G 2 Scroll as needed to the green menu bar and click Document...

Page 78: ...Specifications and Reference Data January 2018 Reference Manual 00809 0400 4101 Rev BA Specifications and Reference Data 70 ...

Page 79: ...tion Change HART Lock Device Lock LOI Password Protection Password Protection Remote Seal Info 1 Num of Remote Seals 2 Seal Type 3 Fill Fluid 4 Diaphragm Material Alarm Levels 1 Alarm Direction 2 High Alarm 3 High Saturation 4 Low Saturation 5 Low Alarm Active Alerts 1 Refresh Alerts 2 Active Alert 1 3 Active Alert 2 4 Etc Sensor Module Info 1 Serial Number 2 Measurement Type 3 Configuration 4 Sen...

Page 80: ...ure Damping 3 Variable Mapping 4 Analog Output 5 Alarm Saturation Values Device Tagging 1 Tag 2 Long Tag 3 Description 4 Message 5 Date Guided Setup 1 Basic Setup 2 Zero Trim 3 Configure Display 4 Scaled Variable 5 Configure Burst Mode Configure Display 1 Pressure 2 Scaled Variable 3 Sensor Temperature 4 Percent of Range 5 Analog Output 6 Review Parameters at Start up Variable Mapping 1 Primary Va...

Page 81: ...ag 2 Long Tag 3 Model 4 Serial Number 5 Date 6 Description 7 Message 8 Model Numbers 9 Manufacturer LOI Password 1 Password Protection 2 Configure Password HART Lock 1 Lock Status 2 Lock Unlock Variable Mapping 1 Primary Variable 2 Second Variable 3 Third Variable 4 Fourth Variable Communication Settings 1 Polling Address 2 Change Polling Address 3 Universal Revision 4 Change HART Revision Burst M...

Page 82: ...ure 1 Pressure 2 Status Scaled Variable 1 Scaled Variable 2 Status Sensor Temperature 1 Sensor Temperature 2 Status Analog Output Analog Output Percent of Range Percent of Range Maintenance 1 Pressure Calibration 2 Analog Calibration 3 Restore Factory Calibration 4 Security 5 Locate Device 6 Device Reset Pressure Calibration 1 Upper Sensor Trim 2 Lower Sensor Trim 3 Zero Trim 4 Damping 5 AO Transf...

Page 83: ...1 Range Values 2 2 2 1 2 2 2 1 Tag 2 2 7 1 1 2 2 7 1 1 Transfer Function 2 2 1 1 6 2 2 1 1 6 Pressure Units 2 2 1 1 4 2 2 1 1 4 Date 2 2 7 1 5 2 2 7 1 4 Descriptor 2 2 7 1 6 2 2 7 1 5 Digital to Analog Trim 4 20 mA Output 3 4 2 1 3 4 2 1 Digital Zero Trim 3 4 1 3 3 4 1 3 Display Configuration 2 2 4 2 2 4 LOI Password Protection 2 2 6 5 2 2 6 4 Loop Test 3 5 1 3 5 1 Lower Sensor Trim 3 4 1 2 3 4 1 ...

Page 84: ...Field Communicator Menu Trees and Fast Keys January 2018 Reference Manual 00809 0400 4101 Rev BA Field Communicator Menu Trees and Fast Keys 76 ...

Page 85: ... RERANGE ENTER VALUES APPLY VALUES BACK TO MENU EXIT MENU LOOP TEST SET 4MA SET 20MA SET CUSTOM END LOOP TEST BACK TO MENU EXIT MENU DISPLAY PRESS on off SCALED on off TEMP on off RANGE on off STARTUP on off BACK TO MENU EXIT MENU EXTENDED MENU CALIBRAT DAMPING TRANSFER FUNCT SCALED VARIAB ASSIGN PV TAG ALARM SAT VALUES PASSWORD SIMULATE HART REV BACK TO MENU EXIT MENU VIEW CONFIG TAG PV PRESS UNI...

Page 86: ... BACK TO MENU EXIT MENU TRANSFER FUNCT LINEAR TRANSFER FUNCTION SQR ROOT TRANSFER FUNCTION BACK TO MENU EXIT MENU SCALED VARIAB VIEW SCALED CONFIG SCALED BACK TO MENU EXIT MENU ASSIGN PV PRESSURE SET PV SCALED SET PV BACK TO MENU EXIT MENU ALARM SAT VALUES ROSEMOUNT VALUES NAMUR VALUES OTHER VALUES BACK TO MENU EXIT MENU PASSWORD ENABLE PASSWORD CHANGE PASSWORD BACK TO MENU EXIT MENU SIMULATE SIMU...

Page 87: ... enter button to select 0 for second digit The third digit from the left will be blinking 00000022 5 Press the enter button to select 0 for the third digit The fourth digit from the left will now be blinking 00000022 6 Press the enter button to select 0 for the fourth digit The fifth digit from the left will now be blinking 00000022 7 Press scroll to navigate through the numbers until the 1 is on ...

Page 88: ...ding on the edited item up to eight locations on the top line can be used for text entry Text entry follows the same rules as the number entry rules in LOI menu tree on page 77 except the following characters are available in all locations A Z 0 9 space Usage note If the current text contains a character the LOI cannot display it will be shown as an asterisk ...

Page 89: ......

Page 90: ...ation Solutions 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 Enquiries AP Emerson com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 4 8865465 RFQ RMTMEA Emerson com Linkedin com company Emerson Automation Solutions Twitter com Rosemount_News Facebook com Rosemoun...

Reviews: