12.3. Einstein Setup for RLDS
Set dip switch 8 to OFF and follow the steps for set-
ting up RLDS units through the Einstein controller in-
terface:
1. Log on.
2. Press F8 for
ACTIONS
.
3. Press Y for
System Setup
.
4. Press 4 for
Network Status/Setup
.
5. Press 2 for
Connected I/O Boards &
Controllers
to open the
Network Setup
screen.
6. Under
Boards on I/O Network
, set the RLDS
number under
IRLDS Controllers
.
7. Press F9
HOME
to go back to the Home
screen.
8. Set the Gateway to 1. Each Gateway can
handle three RLDS controllers, so if four
RLDS controllers are on the network, two
Gateways are needed. The first Gateway will
be address 1 and the RLDS units are numbered
as 1, 2, 3. The second Gateway will be
addressed as 4, but the RLDS is set to 1
because all units on the Gateway are numbered
sequentially 1 to 3. The RLDS controllers are
always numbered 1 to 3 when connected to the
Gateway.
To see a summary of RLDS controllers on the
network:
1. Press F5 for
MORE
.
2. Press L for
Leak Detection
.
3. The leak detectors are listed under
See Summary
. Press the down arrow to
highlight a unit and press Enter to show the
summary of units listed.
The status screen for the selected RLDS controller is
shown.
4. F8 for
ACTIONS
.
5. Press B for
Setup
--you can name the RLDS in the
Name
field.
6. Press the down arrow to the
Num Channels
field to
add the number of zones.
7. Press F10 to go back and see the current status of the
zones.
8. Press F9
HOME
to go back to the Home screen.