System Faults
General Operation of RLDS - UI • 37
network are properly programmed. Check to
ensure that the manifold solenoid cable
connector in each RLDS unit is securely
fastened to its terminal connector. Check for an
illegal parameter. If necessary, reset to the
factory default settings.
8.7.3. Reset to Factory Default
Settings
IMPORTANT
: Performing this function
ERASES all program parameters, alarms, faults,
trends, and log files.
Resetting the RLDS
Press and hold down the
Factory Default
switch in-
side the RLDS (
):
1. Cycle AC power OFF then ON
2. Listen for five beeps
3. Release the switch
Reprogram the RLDS as described in
Programming Setup and UI Navigation for RLDS -
.
8.7.4. Clearing System Faults
If the fault condition is associated with an RLDS, the
monitor will return to normal operation soon after the
problem is corrected. At that time the yellow LED
will turn off and any external alarms connected to the
monitor's alarm relays will also turn off.
Once the system malfunction has been corrected, it
may take some time for the fault condition to clear
completely. If the fault is associated with a specific
zone, the RLDS must first cycle back to the affected
zone before it returns to normal operation. At that
time the yellow LED will turn off and any external
alarms connected to the monitor's alarm relays will
also turn off.
8.7.5. Viewing Fault Log
A data log of the last 20 fault conditions is retained in
memory. On the
Fault screen
) select the
LOG
option to view a display of the Fault Log:
This screen lists potential fault conditions in the left
column and displays a check mark indicating which
problems were associated with each fault
condition as represented by the vertical cursor bar. As
you move the bar horizontally using the left/right
cursor keys, the date and time the fault condition was
detected are displayed in the upper right hand corner
of the display window.
Anytime the fault status changes, there is an entry in
the fault log, both when the fault occurs and when it
is cleared.
The Fault Log can be reset by pressing a
combination of the
ENTER
and right arrow buttons
while viewing the log.
Figure 8-7
- Fault Log Screen