Microprocessor Control
41
Liebert
®
Mini-Mate2
™
MAIN MENU <MENU>
Press the MENU key to display the Main Menu. The menu selections, in order, include:
• SETPOINTS
• STATUS
• ACTIVE ALARMS
• TIME
• DATE
• SETBACK
• SETUP OPERATION
• SETPOINT PASSWORD
• SETUP PASSWORD
• CALIBRATE SENSORS
• ALARM ENABLE
• ALARM TIME DELAY
• COMMON ALARM ENABLE
• CUSTOM ALARMS
• CUSTOM TEXT
• DIAGNOSTICS
• END OF MENU
Use the Up/Down Arrows to scroll through the selections, then when ready to select a particular
function press “Enter”.
6.1.1 Setpoints
Setpoints and system setup parameters are kept in non-volatile memory. Selecting SETPOINTS from
the Main Menu will display the following selections:
• TEMPERATURE SETPOINT
• TEMPERATURE SENSITIVITY
• HUMIDITY SETPOINT
• HUMIDITY SENSITIVITY
• HIGH TEMPERATURE ALARM
• LOW TEMPERATURE ALARM
• HIGH HUMIDITY ALARM
• LOW HUMIDITY ALARM
Scroll through this sub-menu by using the Up/Down Arrows, then press Enter to select a particular
function. To change a particular value, press Enter and use the Up/Down Arrows to change the value.
When the value has been changed press Enter to store the value. For example to change the
temperature setpoint from the main status display.
1. Press Menu key to display main menu.
2. Scroll to “SETPOINTS” using the Up/Down Arrows. Press Enter key.
3. Scroll to “TEMP SETPOINT” using the Up/Down Arrows. Press Enter key.
4. Use the Up/Down Arrows to change the value. Press Enter key.
Table 16
View default setpoints and allowable ranges
Setpoint
Default
Range
Temperature Setpoint
72°F
40-90°F (5-32°C)
Temperature Sensitivity
2.0°F
1-9.9°F (0.6-5.6°C)
Humidity Setpoint
50%
20-80% RH
Humidity Sensitivity
5%
1-30% RH
High Temperature Alarm
80°F
35-95°F (2-35°C)
Low Temperature Alarm
65°F
35-95°F (2-35°C)
High Humidity Alarm
60%
15-85% RH
Low Humidity Alarm
40%
15-84% RH
Summary of Contents for PFH020A-L
Page 3: ......
Page 74: ...Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer User Guide ...
Page 77: ...5 Troubleshooting 37 Vertiv Liebert PFH Installer User Guide ii ...
Page 86: ...Figure 2 6 General piping arrangement Vertiv Liebert PFH Installer User Guide 9 ...
Page 105: ...Vertiv Liebert PFH Installer User Guide 28 This page intentionally left blank ...
Page 109: ...Vertiv Liebert PFH Installer User Guide 32 This page intentionally left blank ...
Page 116: ......