User Manual
Chapter 8
GFK-2843A
Jan 2020
Errors: messages and removal
53
Undervoltage at U
M
:
Supply voltage U
M
is measured. If U
M
< 17 V, a diagnostic
message is generated.
8.3
General errors
Table 21: General errors
Error
cause
Diagnos
tic code
(hex)
LED Remark
Effect
Solution
Ackno
wledg
ment
Device
temperature
at critical
value
X1F2
Immediate
shutdown. Further
temperature
increase causes the
module to switch
to the safe state.
Check and adapt:
–
Ambient conditions
–
Derating
–
Output loads
–
Switching frequency
Yes (4)
Hardware
fault
FS ON Error in the
logic area
Module is in the
safe state
Replacement
Impermissi
ble DIP
switch
position
Module is in the
safe state
Check and correct
switch position
Acknowledgment: yes (4)
Acknowledging the diagnostic message deletes the message.
8.4
Parameterization errors
Table 22: Parameterization errors
Error cause
Diagnosti
c code
(hex)
LED
Remark
Effect
Solution
Ackno
wledg
ment
Incorrect
parameterization
See
Table 23
FS
(flashing)
Each output is
parameterized
individually
Module is
in the
safe state
Check and correct
parameterization.
–
In order to determine what type of parameterization error has occurred, use the
corresponding software to access the controller online and read the error.
Proceed as follows, e.g., in the VersaSafe system:
•
The diagnostic LEDs indicate that an error has occurred.
•
Access the higher-level standard control system online.
For each module of the VersaSafe island, a diagnostic register is mapped to the
process image of the IC220SDL963.
From this, determine the module of the safety island in which an error has occurred.
•
Evaluate the specified diagnostic code.