Assembly, removal, and electrical installation
23
4.1.3
Setting the DIP switches
Important
Set the DIP switches accordingly for your application before assembling the module in an
VersaPoint station. The switches cannot be accessed when the safety terminal is installed
in the VersaPoint station.
The module has a 2-pos. and a 10-pos. DIP switch.
The DIP switches are located on the left-hand side of the safety module.
Figure 6: DIP switches
A
Switch for setting the transmission speed
B
Switch for setting the address (island number)
Important
The numbers located directly on the 10 position DIP switch should be ignored.
When using this switch please refer only to the laser etched numbers on the plastic
housing he module.
2-pos. DIP switch:
The transmission speed is set via the 2-pos. DIP switch.
Left switch transmission speed:
Set the transmission speed:
•
500 kbaud or
•
2Mbaud
The transmission speed is preset to 2 Mbaud.