Detailed Description of I/O Modules
324
Measurement
range
Current (I) /
Voltage (U)
Decimal (D) Hexadecimal Range
Conversion
2 V
0
0x0000
1.8V
-691
0XFD4D
Underloading
1 - 5 V
5.25V
29376
0x72C0
Overloading
D = 27648 x (U
–
1) / 4
U = (D x 4 / 27648) + 1
5 V
27648
0x6C00
Nominal range
3 V
13824
0x3600
1 V
0
0x0000
0.9 V
-691
0XFD4D
Underloading
5.27.7
Measurement Range EP-3124
Measurement
Range
Current (I) /
Voltage (U)
Decimal
(D)
Hexadecimal Range
Conversion
0
–
5 V
5.25 V
29030
0x7166
Overloading
D = 27648 x U/5
I = D x 5 / 27648
5 V
27648
0x6C00
Nominal range
2.5 V
13824
0x3600
0 V
0
0x0000
±5 V
5.25 V
29376
0x72C0
Overloading
D = 27648 x (U
–
1) / 4
U = (D x 4 / 27648) + 1
5 V
27648
0x6C00
Nominal range
2.5 V
13824
0x3600
0 V
0
0x0000
-2.5 V
-13824
0xCA00
-5 V
-27648
0x9400
-5.25 V
-43200
0x5740
Underloading
The following applies for all ranges:
input value > overload range = 0x7FFF
input value < underload range = 0x8000