PACSystems™ RSTi
-EP EPSCPE100 Standalone CPU Quick Start Guide
GFK-3012E
Module Start-up
Power-Up Time
The CPE100 requires at a minimum 35 to 40 seconds to complete power-up. When
power is applied, all the Ethernet Port LEDs blink once. When power up is complete,
the OK LED turns on and remains steady whereas the RUN LED indicates the current
run mode.
Whenever the internal super capacitors are completely discharged, the CPE100
might take approximately 105 seconds to complete the power-up sequence.
Typically, this occurs when the unit is without power for a few days.
You Will Need:
•
This PACSystems standalone controller RSTi-EP CPE100.
•
An external power supply 9-30 VDC provided by a Class II power
supply marked as "double insulated", Limited Power Source
(LPS), or a SELV source with a minimum 32 VDC listed fuse with
3 A max rating is required to power the CPE100.
•
The 3-Way pluggable terminal block which is a mating
connector for the power input terminal block header located on
the front panel of CPE100 comes along with the package. This
mating connector accepts wire sizes 22 to 16 AWG. Screw
torque: 2 in-Ib. Temperature rating for copper wire: 80 °C.
Wiring should be stripped prior to connecting to the mating
connector and cannot exceed 30 m in length.
•
A DIN rail, typically mounted in an enclosure, as discussed above. Alternately,
mount the unit using the (optional) compatible panel-mount adaptor.
•
A computer running PAC Machine Edition (PME) configuration and
programming software. PME Version 9.50 & SIM 1 or later.