PACMotion VFD Syllabus
Section 4
GFK-3167B
December 2020
Modbus/TCP Ethernet Demo (Note 1)
11
Section 4:
Modbus/TCP Ethernet Demo
(
Note 1)
Figure 13: Modbus/TCP Ethernet Configuration
This Demo uses the CPE100 as the Initiating device for Modbus/TCP communications.
VFD Parameters
1.
Set to the following VFD parameter values:
Parameter
Value and Description
P1-12
P1-14
P5-05
4 (Fieldbus)
201 (Extended Menu Access)
0.0 (Disable communication loss timeout)
QuickPanel Plus Ethernet Settings
2.
Set the following IP Address/Mask:
IP address = 192.168.1.7
Subnet mask = 255.255.255.0
VFD Modbus/TCP Option Module settings
3.
Use a DHCP server or the HMS IPConfig software to set the IP address of the
Modbus/TCP module. Use the following settings:
IP address = 192.168.1.5
Subnet mask = 255.255.255.0