ACTUATOR / VALVE COMPATIBILITY 

The P159A Series Actuator is designed for use only with ASCO _158A Series 

Gas Valves or V710_B Series Gas Valves (As shown below):

Specifications  

Force Output: 

 1100 N (250 lbf)

Stroke: 

28.6±1 mm (1-1/8±0.04 in) 

Electrical Characteristics:  

ACTUATOR

Operating 

Voltage/

Frequency

Current, in Amperes

Inrush Opening Holding

P159A1

ON/OFF

120/60

11

1.7

0.06

110/50

11.5

2.1

0.065

240/60

5.0

0.7

0.03

230/50

5.5

1.0

0.035

P159A2

HIGH/LOW/OFF 

120/60

11

1.8

0.12

110/50

11.5

2.2

0.13

240/60

5.0

0.7

0.06

230/50

5.5

1.0

0.07

NOTICE 

The P159A Series Actuator is fitted with a self-resetting thermal cutout device. 

If the recommended temperatures and duty cycles above are exceeded, the 

thermal cutout may trip causing the actuator to stop in its current position 

during valve opening. The valve closing time remains one second or 

less regardless of thermal cutout trip. Once the actuator cools, the cutout 

will self-reset and the actuator will resume operation. If the cutout trips 

repeatedly, verify that the application is within the ambient temperature 

and the duty cycle limits of the actuator. If the application is within the 

specified operating limits and the cutout continues to trip, replace actuator.

INSTALLATION 

Check nameplate for correct catalog number and service. Check the catalog 

number against Figure 1 to ensure that the actuator meets the requirements 

of the application. Contact ASCO for more information about this actuator 

or other actuator options if this actuator is not suitable for your application.

Positioning/Mounting 

Follow the _158A or V710_B Series Gas Valves and/or damper 

manufacturer’s instructions when installing the actuator.
1.  The P159A Series Actuator can be installed to operate in any position.

Figure 2.

 P159A Actuator and _158A or V710_B Gas 

Valve Assembly

Emerson Classification:

Internal

Conduit Hole

(Both Sides)

Valve Stem 

Position Indicator

(Both Sides)

Mounting Set 

Screws

Gas Valve

Figure 2. P159A Actuator and _158A or V710_B Gas Valve Assembly

P159A Actuator

Front Cover 

Screws

Front Cover

Damper Arm

(Optional)

Opening Time:

 

Fast Opening: 

• 

Typical t

ime approximately 9 seconds

• 

At temperatures below -30 °C, actuator may take as long as 30 seconds

Slow Opening: 

• 

Typical time approximately 18 seconds

• 

At temperatures below -30 °C, actuator may take as long as 60 seconds

Maximum Closing Time: 

One second 

Ambient Temperature and Duty Cycle Limitations 

T

he actuator may be operated in ambient temperature conditions from -40 

°C to 66 °C (-40 °F to 150 °F). During normal operation, the P159A series 

Actuator can be cycled CLOSED to OPEN, up to 4 times per hour at maximum 

ambient temperature of 66 °C (150 °F). Higher cycle rates are possible with 

lower ambient temperatures. During commissioning at room temperature  

of  20 °C (68 °F), the actuator can be cycled up to 60 times per hour.

2.  Check to ensure that the mounting gasket, if applicable, is in the proper 

position, clean and without damage. Position the actuator to operate 

the valve 

(and damper if appropriate)

. Secure actuator with the three 

mounting set screws. Tighten set screws t

o 9,0 ± 0,5 N-m (80 ± 5 in-lbs) 

using a 4 mm hex bit socket. Ensure actuator base is fully secured against 

valve body mounting surface for proper operation. (See Figure 2).

Wiring: 

(Refer to Figure 3 for On/Off Actuator & Figure 4 for High/Low/

Off Actuator)

WARNING

 Electrical hazard. To prevent the possibility 

of death, serious injury or property damage, open all 

circuits before inspection, service or disassembly.

AVERTISSEMENT

 Danger électrique. Afin de prévenir 

le risque de décès, de graves blessures ou de dommage 

matériel,  ouvrir  tous  les  circuits  avant  l’inspection,  la 

maintenance ou le démontage.

*  Actuator to be installed on upstream valve position (Closest to valve inlet 

port) 

** Actuator to be installed on downstream valve position (Closest to valve 

outlet port)

Actuator Actuator Electrical 

Options

Valve/Seal Type Valve Catalog #

P159A1

ON/OFF

P159A1_ _X_X_1_ _

P159A1_ _X_X_2_ _

P159A1_ _X_X_5_ _

_158A

Standard Trim

_158A1 OR 

_158A5 OR 

_158A7* OR

_158AA* OR

_158AC*

P159A1_ _X_X_3_ _

P159A1_ _X_X_4_ _

_158A

Standard with Seal 

Overtravel Trim

_158A2 OR 

_158A6 OR 

_158A8* OR 

_158AA**

P159A1_ _X_X_1_ _

P159A1_ _X_X_2_ _

P159A1_ _X_X_5_ _

V710_B

Quick Opening 

(Standard) Trim

V710_B_

P159A1_ _X_X_3_ _

P159A1_ _X_X_4_ _

V710_B

Quick Opening with 

Valve Seal Overtravel 

Trim

V710_B_V22

P159A2

HIGH/

LOW/

OFF

P159A2_ _X_X_1_ _

P159A2_ _X_X_2_ _

_158A

Linear Trim

_158A3 OR 

_158A7**

P159A2_ _X_X_3_ _

_158A

Linear with Seal 

Overtravel Trim

_158A4 OR 

_158A8** OR 

_158AC**

P159A2_ _X_X_1_ _

P159A2_ _X_X_2_ _

V710_B

Linear Trim

V710_B_V15

P159A2_ _X_X_3_ _

V710_B 

Linear with Valve

Seal Overtravel Trim

V710_B_V25

Summary of Contents for P159A Series

Page 1: ...er to the dump valve thus stabilizing hydraulic pressure to hold shaft position Position indicators on both sides of the actuator show the actual position of the valve stem Upon power interruption the dump valve opens releasing hydraulic pressure and allowing the return spring to retract the stem and close the valve fully Closing time is one second or less SERIES P159A P159A2 HIGH LOW OFF ACTUATOR...

Page 2: ...e as long as 30 seconds Slow Opening Typical time approximately 18 seconds At temperatures below 30 C actuator may take as long as 60 seconds Maximum Closing Time One second Ambient Temperature and Duty Cycle Limitations The actuator may be operated in ambient temperature conditions from 40 C to 66 C 40 F to 150 F During normal operation the P159A series Actuator can be cycled CLOSED to OPEN up to...

Page 3: ...al saddle provided in the housing below the hot and neutral power terminals 4 Power Terminal Screw Torque 1 4 N m 12 in lbs Ensure all strands are securely fastened under terminal screw Ground Screw Torque 2 3 N m 20 in lbs Ensure all strands are securely fastened under saddle clamp 5 Using stranded 12 18 AWG wire connect wiring from an external high fire switch not supplied to the 3 position term...

Page 4: ...ghtening Torque screws to 1 4 to 1 8 N m 12 to 16 in lbs evenly using crisscross pattern Figure 6 Auxiliary Switch Adjustment Adjust this screw using 2 5 mm Allen key Auxiliary Switch Assembly Emerson Classification Internal Figure 7 Low Fire Switch Adjustment Adjust this screw using 2 5 mm Allen key Low Fire Switch Assembly Figure 7 Low Fire Switch Adjustment Refer to Figure 7 1 Before removing t...

Reviews: