Chapter 5 Use Of Monitoring Module M800D 77
Note
*
:
R means OID is read-only (GET). W means OID is writable. R/W means OID can be read and modified (GET/SET)
5.4.2 Access M800D through NMS
The following part introduces how to access M800D with HP OpenView as an example.
Apply administrative authority
In order to use NMS to manage the devices connected to M800D, the administrative authority needs to be applied for
the NMS, that is, add the NMS information to the access list of SNMP agent.
Add NMS through Web browser
Refer to
for the method of adding NMS.
5.5 Parameter Setting Guidance
5.5.1 Rectifier Parameters
M800D monitoring module could work with MINI/SMALL/MEDIUM/LARGE capacity rectifiers. For each type of
rectifiers, the following parameters should be set correctly.
Table 1.1 Rectifier Type Related Parameters
Parameter
Range
Default
Step change
Rated Current
NA
50
Rectifier Power type
Double
Single
Small
Double
AC phases
Single phase
Three phases
Single Phase
Rated Current should be set according to the actual power of rectifier. Rectifier power and AC phases should be set
according to the following table:
Table 1.2 Rectifier power and AC phases
Capacity type (model)
Rectifier Power type
AC phases
MINI (R48-800, R48-400)
Single phase
Single
SMALL (R48-1800, R48-1800A)
Single phase
Small
MEDIUM (R48-2900U, R48-3200)
Single phase
Double
LARGE (R48-5800)
Three phases
Double
5.5.2 Battery Management Parameters
Battery test parameters
Table 1.1 Battery test parameters
Parameter
Range
Default
Step change
Constant Current Test Enabled
Yes/No
No
-
Planned Test Enabled
Yes/No
Yes
-
Date of Planned tests
Jan 1, 0 O’clock
Apr 1, 0 O’clock
Jul 1, 0 O’clock
Oct 1, 0 O’clock
Mains Failure Test Enabled
Yes/No
Yes
Short Test Enabled
Yes/No
Yes
-
Max Difference Current For Short Test
0 to 1.0 C
10
0.05 C
10
0.01
Short Test Duration
1 to 30 min
5 min
1 min
Test End Time
10 to 1440 min
180 min
10 min
Test End Voltage
-43 to –50V
-45.2V
0.1V
Test End Capacity
30 to 100 %
30 %
1 %
Test Current (for Constant Current Test)
10 to 10000 A
10000 A
10 A
Short Test Start Condition
0 to 365 Days
30 Day
1 Day
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual