33
Reference Manual
24625020, Rev AA
Installing the Electronics Control Unit
March 2017
Installing the Electronics Control Unit
Figure 3-13. 'Two-out-of-two' Configuration Using Normally-open Contacts (Hydratect 2462 A and C)
A. To trip device.
B. Relays shown in de-energized state (see
C. To alarm annunciator.
3.5.3
Preparing the fault and status relay cables
(for the Hydratect 2462E)
The Hydratect 2462 Electronics Control Unit (“Control Unit”) uses normally-open and
normally-closed switch outputs for fault and status indication.
The outputs are available on a pair of 14-way Klippon connectors: PL204 and PL404.
Procedure for making connections to the switched outputs
1.
Remove the front panel from the Control Unit case and store it in a safe place.
(This is described in detail on
“Fitting cable glands” on page 22
. The panel has
mounted on it all the electronic circuitry and must be protected against adverse
conditions such as heat, dust, and static electricity).
2.
Route the fault/status cable from the external equipment to the Control Unit
through suitable ducting (conduit).
3.
Assemble the cable gland and fit it to the underside of the Control Unit.
Screened cables must be used. Ensure there is a good annular (ring-shaped)
contact between the cable screen and cable gland. Allow for cable conductors of
length 300 mm inside the Control Unit, and twist the power pairs together.
C
A
B
PL204 (Channel 1)
PL404 (Channel 2)
N. O.
Status
N. O.
Fault
N. O.
Status
N. O.
Fault
8
7
4
3
8
7
4
3
Summary of Contents for Mobrey Hydratect 2462
Page 2: ......
Page 16: ...10 Reference Manual 24625020 Rev AA Introduction March 2017 Introduction ...
Page 52: ...46 Reference Manual 24625020 Rev AA System Testing March 2017 System Testing ...
Page 62: ...56 Reference Manual 24625020 Rev AA Electronics Servicing March 2017 Electronics Servicing ...
Page 65: ......