28
LF-Series Flowmeters: Sensor/Transmitter Installation
I/O Wiring – FM AN Transmitters
Figure 6-1
Basic analog wiring
Figure 6-2
HART/analog single-loop wiring
+
–
mA output loop
820
Ω
maximum loop resistance
Frequency receiving device
+
–
00042
Output voltage level is +24 VDC ± 3%
820
Ω
maximum loop resistance
For HART communications:
• 600
Ω
maximum loop resistance
• 250
Ω
minimum loop resistance
+
–
HART-
compatible host
or controller