
Quick start with ProLink II
Figure 3-2
ProLink II connection to HART clips
A
B
D
C
A
PC
B
HART interface
C
250–600 Ω resistance
D
Transmitter
Notes
•
This figure shows a serial port connection. A USB port connection is also available.
2.
To connect to a point in the local HART loop, attach the leads from the signal converter to any
point in the loop and add resistance as necessary. See Figure 3-3 .
ProLink II must be connected across a resistance of 250–600 Ω.
30
Micro Motion 9739 MVD Transmitters