Integrate the meter with the control system
Tip
Set the
URV
to match the upper range value at the remote device.
7.6
Configure digital communications
Display
N/A
ProLink II
ProLink→Configuration→Device→Digital Comm Settings
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Communications
The digital communications parameters control how the transmitter will communicate using digital
communications.
The 9739 MVD supports the following types of digital communications:
• HART/Bell 202 over the primary mA terminals
• HART/RS-485 over the RS-485 terminals
• Modbus/RS-485 over the RS-485 terminals
• Modbus RTU via the service port
Note
The service port responds automatically to a wide range of connection requests. It is not configurable.
Important
The service port clips on the user interface of the 9739 MVD transmitter are directly connected to
RS-485 terminals (26 and 27). If you wire the transmitter for RS-485 digital communications, you cannot
use the service port clips for communication with the transmitter.
7.6.1
Configure HART/Bell 202 communications
Display
N/A
ProLink II
ProLink→Configuration→Device→Digital Comm Settings
Field Communicator
Configure→Manual Setup→Inputs/Outputs→Communications→HART Communications
HART/Bell 202 communications parameters support HART communication with the transmitter's primary
mA terminals over a HART/Bell 202 network.
The HART/Bell 202 communications parameters include:
•
HART Address
(
Polling Address
)
•
Loop Current Mode
(ProLink II) or
mA Output Action
(Field Communicator)
•
Burst Parameters
(optional)
•
HART Variables
(optional)