10 Complete the configuration
10.1 Test or tune the system using sensor simulation
Display
Menu
>
Startup Tasks
>
Commissioning Tools
>
Sensor Simulation
ProLink III
Device Tools
>
Diagnostics
>
Testing
>
Sensor Simulation
Field Communicator
Service Tools
>
Simulate
>
Simulate Sensor
Use sensor simulation to test the system's response to a variety of process conditions, including boundary
conditions, problem conditions, or alert conditions, or to tune the loop.
Prerequisites
Before enabling sensor simulation, ensure that your process can tolerate the effects of the simulated process
values.
Procedure
1. Enable sensor simulation.
2. For mass flow, set
Wave Form
as desired and enter the required values.
Option
Required values
Fixed
Fixed Value
Sawtooth
Period
Minimum
Maximum
Sine
Period
Minimum
Maximum
3. For density, set
Wave Form
as desired and enter the required values.
Option
Required values
Fixed
Fixed Value
Sawtooth
Period
Minimum
Maximum
Sine
Period
Minimum
Maximum
4. For temperature, set
Wave Form
as desired and enter the required values.
Configuration and Use Manual
Complete the configuration
MMI-20048166
April 2019
Configuration and Use Manual
115