Note
For some faults only: If
Last Measured Value Timeout
is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
Procedure
1.
Set
Frequency Output Fault Action
as desired.
The default value is
Downscale
(0 Hz).
2.
If you set
Frequency Output Fault Action
to
Upscale
, set
Frequency Fault Level
to the desired
value.
The default value is 15000 Hz. The range is 10 to 15000 Hz.
Options for Frequency Output Fault Action
Options for Frequency Output Fault Action
Table 6-8:
Label
Frequency output behavior
Upscale
Goes to configured
Upscale
value:
•
Range: 10 Hz to 15000 Hz
•
Default: 15000 Hz
Downscale
0 Hz
Internal Zero
0 Hz
None
(default)
Tracks data for the assigned process variable; no fault action
CAUTION!
If you set
mA Output Fault Action
or
Frequency Output Fault Action
to
None
, be sure to set
Digital
Communications Fault Action
to
None
. If you do not, the output will not report actual process data,
and this may result in measurement errors or unintended consequences for your process.
Restriction
If you set
Digital Communications Fault Action
to
NAN
, you cannot set
mA Output Fault Action
or
Frequency
Output Fault Action
to
None
. If you try to do this, the transmitter will not accept the configuration.
6.4
Configure the discrete output
The discrete output is used to report specific flowmeter or process conditions. The discrete
output parameters control which condition is reported and how it is reported. Your
transmitter may have zero or one discrete output: Channel B can be configured as a
frequency output or a discrete output.
The discrete output parameters include:
•
Discrete Output Source
Integrate the meter with the control system
114
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Summary of Contents for MICRO MOTION 2700
Page 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Page 373: ......