This parameter defines the action to be taken for a timeout on the receive link.
This parameter defines the slot in which an event will occur if a cyclic data timeout occurs on the
receive link.
S.10.046
Rx1 Link Timeout Action
S.10.056
Rx2 Link Timeout Action
S.10.066
Rx3 Link Timeout Action
Minimum
0
Maximum
2
Default
0
Units
ms
Type
8 Bit User Save
Update Rate
Read on reset
Display Format
None
Decimal Places
0
Coding
RW, BU
Value
Text
Description
0
Trip
Trip drive with Slot
x
Error and sub-trip code yyy, where x is the
slot number in which the module is installed.
1
Send flt values
Send configured fault values to the output parameters
2
Clear output
PLC output parameters will have their values set to zero
S.10.047
Rx1 Link Timeout Event Destination
S.10.057
Rx2 Link Timeout Event Destination
S.10.067
Rx3 Link Timeout Event Destination
Minimum
0
Maximum
4
Default
0
Units
Type
8 Bit User Save
Update Rate
Read on reset
Display Format
None
Decimal Places
0
Coding
RW, Txt, BU
Value
Text
Description
0
This slot
Trigger module event in this slot
1
Slot 1
Trigger module event in slot 1
2
Slot 2
Trigger module event in slot 2
3
Slot 3
Trigger module event in slot 3
4
Slot 4
Trigger module event in slot 4