Enable Communication Protocols
21
Liebert
®
IntelliSlot
™
Unity
™
Card User Manual
3.1.2.2 Configure BACnet MSTP Protocol
1. Select
Communications
tab >
Protocols
>
BACnet MSTP
.
2. Click
Edit
and enter a user name and password if required.
3. Set the BACnet MSTP
Node ID
.
• The Node ID defaults to 1, but must have a value from 1 to 255 that is unique among devices
connected through the RS-485 interface.
4. Set the BACnet MSTP
Data Rate
.
5. Set the BACnet MSTP
Max Master Address
.
6. Set the BACnet MSTP
Max Info Frames
.
For descriptions of the settings, see
.
7. Click
Save
to confirm the changes or
Cancel
to discard them.
8. Restart the card to activate the changes.
a. Select
Communications
tab >
Support
.
b. Enable the commands.
c. Click
Restart
.
Figure 3-6 BACnet MSTP
NOTE
Contact your system administrator if you are uncertain about the settings.
Node ID must
be unique on
the RS-485 bus
this card is
connected to.