Enable Communication Protocols
Liebert
®
IntelliSlot
™
Unity
™
Card User Manual
20
3.1.2.1 Configure BACnet IP Protocol
1. Select
Communications
tab >
Protocols
>
BACnet IP
.
2. Click
Edit
and enter a User name and password if required.
3. Set the
BACnetIP/Port Number
.
If the Liebert IntelliSlot Unity card is on a different subnet (a possibility when the monitored units are
part of a Liebert SiteScan network or other third-party monitoring service):
a. Choose whether or not to enable
Register as Foreign Device
.
b. Enter the
IP address of the BBMD
(BACnet Broadcast Management Device).
c. Enter a time in seconds for
Foreign Device Time-to-Live
.
For descriptions of the settings, see
.
4. Click
Save
to confirm the changes or
Cancel
to discard them.
5. Restart the card to activate the changes.
a. Select the
Communications
tab >
Support
.
b. Enable the commands.
c. Click
Restart
.
Figure 3-5 BACnet IP
NOTE
Contact your system administrator if you are uncertain about the settings.
Summary of Contents for Liebert Intellislot Unity Card
Page 1: ...Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 ...
Page 2: ......
Page 6: ...Liebert IntelliSlot Unity Card User Manual iv Page intentionally left blank ...
Page 8: ...Liebert IntelliSlot Unity Card User Manual vi Page intentionally left blank ...
Page 10: ...Liebert IntelliSlot Unity Card User Manual viii Page intentionally left blank ...
Page 16: ...Introduction Liebert IntelliSlot Unity Card User Manual 6 Page intentionally left blank ...
Page 88: ...Firmware Updates Liebert IntelliSlot Unity Card User Manual 78 Page intentionally left blank ...
Page 91: ......