3.10 Wellness—Next Maintenance Calculation
The next maintenance calculation, as well as the diagnostics feature, will help keep the cooling unit
running at peak performance to ensure minimum component stress and maximum reliability. The
diagnostics will help the service engineer evaluate the unit’s operation since the last maintenance.
3.10.1 Calculating Next Maintenance and Diagnostics
If the unit includes any of the following components, they are included in the calculation:
• Fan(s)
• Compressor 1
• Compressor 2
• Electric Heaters
• Humidifier
For each component, the next maintenance will be calculated from the following parameters:
• Standard service interval (1, 2 or 4 times a year) (to be set)
• Working hours (counted)
• Number of starts (counted)
• Average running time (calculated)
• Optimum number of starts per hour (to be set)
• Maximum number of starts per hour (to be set)
• Maximum bonus to enlarge time to next maintenance (to be set)
• Maximum penalty to reduce time to next maintenance (to be set)
Calculating Unit Wellness
Figure 47 Wellness—Basic settings screen, page 1 of 9
To confirm that preventive maintenance has been performed:
1. Go to line Service>Wellness>basic settings>S007 and select YES.
2. Press the enter button. This will confirm the preventive maintenance. Line S005 will change to
the date of the preventive maintenance was performed. Line S008 will update to show the next
calculated maintenance date.
Liebert iCOM keeps tabs on the condition of a cooling unit, determining its wellness and projecting
when service will be needed, for the entire unit as well as for individual components. This assists in
scheduling maintenance calls and helps pinpoint components likely to require service.