Operation
67
Liebert
®
iCOM
®
for Liebert DSE
™
Table 21
Alarms specific to Liebert DSE compressor
Tandem Specific Alarms
Description
COMP 1A OVERLOAD
The compressor has entered an overload condition and has been deactivated.
COMP 1B OVERLOAD
COMP 2A OVERLOAD
COMP 2B OVERLOAD
COMP 1A HRS EXCEEDED
The run hour limit has been exceeded by the actual run hours of the
compressor.
COMP 1B HRS EXCEEDED
COMP 2A HRS EXCEEDED
COMP 2B HRS EXCEEDED
COMP 1A HIGH TEMP
The compressor has entered into a high temperature condition and has been
deactivated.
COMP 1B HIGH TEMP
COMP 2A HIGH TEMP
COMP 2B HIGH TEMP
COMP 1A DISCH SENSOR FAIL
The compressor discharge pressure sensor has failed.
COMP 1B DISCH SENSOR FAIL
COMP 2A DISCH SENSOR FAIL
COMP 2B DISCH SENSOR FAIL
COMP 1A SHORT CYCLE
The compressor has exceeded the maximum number of stop / starts in the
time period allowed.
COMP 1B SHORT CYCLE
COMP 2A SHORT CYCLE
COMP 2B SHORT CYCLE
CIRCUIT 1 HIGH PRESS
—
CIRCUIT 2 HIGH PRESS
—
CIRCUIT 1 LOW PRESS
—
CIRCUIT 2 LOW PRESS
—
EEV COMMUNICATION ERROR
Communications between EEV and the Liebert iCOM control board cannot be
established. Check CANbus cable to EEV.
EEV SENSOR ERROR
Sensor is either disconnected or has failed. Check connection from all sensors
to EEV board.